Studer Innotec XTH 8000-48 Manual Do Utilizador

Página de 36
STUDER Innotec 
Xtender 
Installation and operating Instructions 
Xtender V1.3 
Page 24 
 
Auto restart
Absorption
Float
Input limited
Load search
Overload
Overtemp.
Bat. over volt.
Multimode Power Centre
Blinking indicator
XTH-5000-24
Inverter + Charger + Autom. transfer + Input current manager 
46
45
44
43
42
41
6.4.2  BTS-01
 TEMPERATURE SENSOR
 
The operating voltages for lead batteries vary depending on the 
temperature. A temperature sensor is optionally available to correct the 
battery voltage and guarantee an optimum charge whatever the battery 
temperature. The correction factor given by the correction of the sensor is 
set by the configuration {1139} 
Article no. for the temperature sensor (including a cable of 3 m): BTS-01.   
Dimensions: H x W x D / / 58 x 51.5 x 22 mm 
 
 
 
7
  Control 
7.1
  Main on/off control 
This switch (1) interrupts the electronic supply and all the 
Xtender peripherals. The residual consumption on the 
battery is therefore less than 1 mA. 
The ON/OFF switch is used only for the complete 
stoppage of the whole system.  
7.2
  Display and control parts 
The Xtender has a ON/OFF button and light indicators at 
the front of the device, allowing clear identification of 
the operating mode. 
(41)  The ON/OFF button allows the startup or 
complete stoppage of the system such as it has been 
programmed. In the systems comprising several units, 
each unit is started or stopped individually. For a 
simultaneous startup of all the units use the dry contact 
control (see chap. 6.2.12 – p. 21) or the ON/OFF 
button of the RCC-02/03 remote control. 
 
 
 
Even when the equipment has stopped, 
dangerous voltages may be present at the 
Xtender input.  
 
(42)  This indicator lights up when the equipment has been stopped manually using the ON/OFF 
button (41). It also allows the cause of an unintentional stoppage of the device to be indicated via 
the different flashes, the imminence of a stoppage or the temporary limitation of its performance.  
The table below describes the type of fault according to the number of flashes on the indicator (42) 
 
 
 
Indicated alarm
 
Comment
 
1x (Imminent) stoppage as a 
result of low battery voltage. 
If the device has not yet stopped, it is recommended to 
disconnect all non-priority consumers and/or start up the 
generator. If the Xtender has stopped it will restart 
automatically when the battery voltage has reached the correct 
value again {1110}. It can be restarted manually using the 
ON/OFF button (41) as long as the battery voltage is higher 
than the critical threshold {1488}. 
See also chapter 6.2.9 – p. 20.