 P33-4 Zero Clearance Direct Vent Gas Fireplace
11
EXTERIOR VENT TERMINATION LOCATIONS
INSTALLATION
A=  Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm) 
B=  Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm)
C=  Clearance to permanently closed window *(min. 12"/30cm)
D=  Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of (24"/60cm) from the centerline of the terminal 
(min. 18"/46cm) check with local code.
E=  Clearance to unventilated soffi t (min. 15"/38cm)
F=  Clearance to outside corner: with AstroCap Termination Cap (min. 6"/15cm), with Dura-Vent Termination Cap (12"/30cm)
G= Clearance to inside corner: with AstroCap Termination Cap (min. 6"/15cm), with Dura-Vent Termination Cap (12"/30cm)
H=  Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally from the centerline of the regulator.
J=  Clearance to service regulator vent outlet *(min. 36"/90cm)
K=  Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance *(12"/30cm) #(9"/23cm)
L=  Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
 #3' 
(91cm) above if within 10' (3m) horizontally.
M= Clearance above paved sidewalk or a paved driveway located on public property *(min. 84"/2.1m)
N=  Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)   
Note: 
- A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both 
dwellings.
- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
- If the vent termination is accessible, a certifi ed guard shall be installed.
* As specifi ed in CGA B149 Installation Code.  Note: Local codes or  regulations may require different clearances.
# In accordance with the current ANSI Z223.1/NFPA 54, Natioinal Fuel Gas Code.