8.1.  Installation
[Fig. 8.1.1] (P.3)
<A>  Without detachable leg
<B> With detachable leg
A
M10 anchor bolt procured at the site. B Corner is not seated.
C
Fixing bracket for the hole-in anchor bolt (3 locations to fix with screws).
D
Detachable leg
Fix unit tightly with bolts so that unit will not fall down due to earthquakes or 
• 
strong winds.
Use concrete or an angle bracket as the foundation of unit.
• 
Vibration may be transmitted to the installation section and noise and 
• 
vibration may be generated from the floor and walls, depending on the 
installation conditions. Therefore, provide ample vibrationproofing (cushion 
pads, cushion frame, etc.).
Build the foundation in such way that the corner of the installation leg is 
• 
securely supported as shown in the figure. (Fig. 8.1.1) 
When using a rubber isolating cushion, please ensure it is large enough to 
cover the entire width of each of the unit's legs. If the corners are not firmly 
seated, the installation feet may be bent.
The projecting length of the anchor bolt should be less than 30 mm.
• 
Hole-in anchor bolts are not compatible with this product. However, if fixing 
• 
brackets are mounted on the 4 locations (6 locations: P450, EP300) of the 
unit attachment part, hole-in anchor bolts can be used.
[Fig. 8.1.2] (P.3)
A
Screws
The detachable leg can be removed at the site.
• 
Detaching the detachable leg
• 
 
Loosen the three screws to detach the detachable leg (Two (three: P450, 
EP300) each in the front and back).
 
If the base leg finish is damaged when detaching, be sure to repair at the 
site.
 Warning:
Be sure to install unit in a place strong enough to withstand its weight.
• 
Any lack of strength may cause unit to fall down, resulting in a 
personal injury.
Have installation work in order to protect against strong winds and 
• 
earthquakes.
Any installation deficiency may cause unit to fall down, resulting in a 
personal injury.
When building the foundation, give full attention to the floor strength, drain water 
disposal <during operation, drain water flows out of the unit>, and piping and 
wiring routes.
Precautions when routing the pipes and wires below the unit (Without 
detachable leg)
When routing the pipes and wires below the unit, be sure that the foundation and 
base work do not block the base through-holes. Also make sure the foundation 
is at least 100 mm high so that the piping can pass under the unit.
8.  Installation of unit
9.  Refrigerant piping installation
The pipe is connected via a terminal-branch type connection in which refrigerant 
piping from the outdoor unit is branched at the terminal and is connected to each 
of the indoor units.
The method of pipe connection is as follows: flare connection for the indoor 
units, gas pipes and liquid pipes for outdoor units, brazed connection. Note that 
the branched sections are brazed.
 Warning:
Always use extreme care to prevent the refrigerant gas from leaking while 
using fire or flame. If the refrigerant gas comes in to contact with a flame 
from any source, such as a gas stove, it breaks down and generates 
a poisonous gas which can cause gas poisoning. Never weld in an 
unventilated room. Always conduct an inspection for gas leakage after 
installation of the refrigerant piping has been completed.
 Caution:
Do not vent R410A into the atmosphere.
• 
R410A is a Fluorinated Greenhouse gas, covered by the Kyoto Protocol 
• 
with a Global Warming Potential (GWP) = 1975.
9.1.  Caution
This unit uses refrigerant R410A. Follow the local regulations on materials and 
pipe thickness when selecting pipes. (Refer to the table on the right.)
1
  Use the following materials for refrigeration piping.
Material: Use copper alloy seamless pipes made of phosphorus 
• 
deoxidized copper. Ensure the inner and outer surfaces of the pipes are 
clean and free from hazardous sulfur, oxide, dusts, shaving particles, oils, 
and moisture (contamination).
Size: Refer to item 9.2. for detailed information on refrigerant piping 
• 
system.
2
  Commercially available piping often contains dust and other materials.  
Always blow it clean with a dry inert gas.
3
  Use care to prevent dust, water or other contaminants from entering the 
piping during installation.
4
  Reduce the number of bending portions as much as possible, and make 
bending radii as big as possible.
5
  For indoor and outdoor branching, be sure to use the following twinning pipe 
sets (sold separately).
Copper pipe size and radial thickness for R410A CITY MULTI.
Size (mm)
Size (inch)
Radial thickness (mm)
Pipe type
ø6.35
ø1/4"
0.8
Type-O
ø9.52
ø3/8"
0.8
Type-O
ø12.7
ø1/2"
0.8
Type-O
ø15.88
ø5/8"
1.0
Type-O
ø19.05
ø3/4"
1.2
Type-O
ø19.05
ø3/4"
1.0
Type-1/2H or H
ø22.2
ø7/8"
1.0
Type-1/2H or H
ø25.4
ø1"
1.0
Type-1/2H or H
ø28.58
ø1-1/8"
1.0
Type-1/2H or H
ø31.75
ø1-1/4"
1.1
Type-1/2H or H
ø34.93
ø1-3/8"
1.2
Type-1/2H or H
ø41.28
ø1-5/8"
1.4
Type-1/2H or H
*  For pipe sized ø19.05 (3/4") for R410A air conditioner, choice of pipe type is 
up to you.
Indoor twinning pipe set model
Line branch
Header branch
Lower stream unit 
model
Less than 200 in total
Lower stream unit model
More than 201 and less 
than 400 in total
Lower stream unit model
More than 401 and less 
than 650 in total
Lower stream unit model
More than 651 in total
4 branching
8 branching
10 branching
CMY-Y102S-G2
CMY-Y102L-G2
CMY-Y202-G2
CMY-Y302-G2
CMY-Y104-G
CMY-Y108-G
CMY-Y1010-G
Outdoor twinning kit model
Total outdoor model
P500 ~ P650  
EP400 ~ EP600
Total outdoor model
P700 ~ P900
Total outdoor model
P950 ~ P1250
EP650 ~ EP900
CMY-Y100VBK2
CMY-Y200VBK2
CMY-Y300VBK2