T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
3
63-2605—5
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do not 
include normal manufacturing tolerances. Therefore, 
this unit might not exactly match listed specifications. 
This product is tested and calibrated under closely 
controlled conditions; minor performance differences 
can be expected if those conditions are changed.
Models: See Table 1.
Dimensions: See Fig. 1.
Finish (color): Trident White.
Batteries: No batteries required.
Table 1. T7350 Thermostat Features.
a
All models are down-selectable and can be configured to control fewer stages than the maximum allowed.
b
One extra stage (of either heat or cool) can be configured using the auxiliary relay.
c
Heat pump applications for these models have a maximum of two heat stages and two cool stages.
Mounting Means:
Mounts on subbase.
Subbase Mounts On:
Wall: Using two 5/8 in. long #6-32 screws (included).
Outlet Box: Using sheet metal screws.
Throttling Range for Modulating Outputs:
Automatically adjusts based on heat/cool stages. Manually 
adjustable with PDA.
Clock Accuracy (at 77° F [25° C]): ±1 min./month (30 days).
Minimum Stage Operation Time (fixed):
Minimum On
Heat: 1 minutes.
Cool: 3 minutes.
Minimum Off (Cool and Heat Pump): 1 minute.
Electrical Ratings:
Power: 24 Vac, 50/60 Hz.; 20 to 30 Vac, 50/60 Hz.
Input:
Temperature: 20K ohms.
Humidity: 0-10 Vdc.
Outdoor: 3000 PTC.
Discharge Air: 20K ohms.
Occupancy Sensor: Dry contact switching 30 Vdc at 1 mA.
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum.
Inrush: 7.5A maximum.
Modulating Output: 4 to 20 mA with 510 ohm maximum 
terminating resistance.
System Current Draw (without load):
5 VA maximum at 30 Vac, 50/60 Hz.
NOTE: Relays are N.O. Single-Pole, Single-Throw (SPST).
Outdoor Sensor Wiring: Requires 18 gauge wire.
Humidity Ratings: 5% to 90% RH, noncondensing.
Emergency Heat Indication:
Display indicates when Emergency Heat is activated (Em).
Temperature:
Ratings:
Operating Ambient: 30°F to 110°F (-1°C to 43°C).
Shipping: -30°F to +150°F (-34°C to +66°C).
Display Accuracy: ±1°F (±1°C).
Setpoint:
Range:
Heating: 40°F to 90°F (4°C to 32°C).
Cooling: 45°F to 99°F (7°C to 37°C).
Deadband: 2°F (1°C).
Loss of Power: The thermostat maintains programmed times 
and temperatures for the life of the product. Clock and day 
information is retained for a minimum of 48 hours.
NOTE: To achieve the 48-hour power-loss clock retention, 
the T7350 must be powered for at least 5 minutes.
Communicating Model T7350H:
Connection Terminals for the LonWorks Bus.
Network jack for quick access by personal computer based 
tools.
Communications service-pin pushbutton to simplify startup.
 LonMark Functional Profile: 8500_20 Space Comfort 
Controller.
LonMark SCC Object Type: 8504 Rooftop See Fig. 2.
LonMark Program Identifier: 80:00:0C:55:04:03:04:2E.
LonMark Application Interoperability: version 3.3
Honeywell LonMark Plug-In file downloads: 
http://plugin.ge51.honeywell.de/index.htm#
Model
Applications
Maximum Stages
a
Features
Auxiliary
Relay
L
ON
W
ORKS
® 
Capability?
Heat
Cool
T7350A
Conventional
 or
 Heat Pump
1
b
1
b
Yes
No
T7350B
2
b
2
b
Outdoor, Discharge Air Capability
Yes
T7350D
3 (2)
c
3 (4)
c
Humidity, Occupancy, 
Outdoor, Discharge Air Capability
Yes
T7350H1009
Isolated 
Normally 
Open
Yes
T7350H1017 Modulating
2 modulating, 2
b
 relay Humidity, Occupancy, 
Outdoor, Discharge Air Capability, 
4-20 mA output (2-10 Vdc with 500 ohm resistor)
Yes
T7350M
Yes
No