Water Damage Hazard
Temperature-Pressure Relief Valve discharge
pipe must terminate at adequate drain.
CAUTION
T&P VALVE DISCHARGE PIPE REQUIREMENTS:
•  Shall not be smaller in size than the outlet pipe size of the valve, 
or have any reducing couplings or other restrictions.
•  Shall not be plugged or blocked.
•  Shall not be exposed to freezing temperatures.
•  Shall be of material listed for hot water distribution.
•  Shall be installed so as to allow complete drainage of both the 
Temperature-Pressure Relief Valve and the discharge pipe.
•  Must  terminate  a  maximum  of  six  inches  (15.2  cm)  above  a 
floor  drain  or  external  to  the  building.  In  cold  climates,  it  is 
recommended  that  the  discharge  pipe  be  terminated  at  an 
adequate drain inside the building.
•  Shall  not  have  any  valve  or  other  obstruction  between  the 
temperature-pressure relief valve and the drain.
Burn hazard.
Hot water discharge.
Keep clear of Temperature-
Pressure Relief Valve
discharge outlet.
The  Temperature-Pressure  Relief  Valve  must  be  manually 
operated  at  least  twice  a  year.  Caution  should  be  taken  to 
ensure that (1) no one is in front of or around the outlet of the 
Temperature-Pressure  Relief  Valve  discharge  line,  and  (2) 
the  water  manually  discharged  will  not  cause  any  bodily  injury 
or  property  damage  because  the  water  may  be  extremely  hot. 
If after manually operating the valve, it fails to completely reset 
and continues to release water, immediately close the cold water 
inlet  to  the  water  heater,  follow  the  draining  instructions  in  this 
manual, and replace the Temperature-Pressure Relief Valve with 
a properly rated/sized new one.
NOTE: The purpose of a Temperature-Pressure Relief Valve is to 
prevent excessive temperatures and pressures in the storage tank. 
The  T&P  valve  is  not  intended  for  the  constant  relief  of  thermal 
expansion.  A  properly  sized  thermal  expansion  tank  must  be 
installed  on  all  closed  systems  to  control  thermal  expansion,  see 
Closed Water Systems and Thermal Expansion on Page 21.
If you do not understand these instructions or have any questions 
regarding  the  Temperature-Pressure  Relief  Valve  call  the  toll 
free number listed on the back cover of this manual for technical 
assistance.
TEMPERATURE-PRESSURE RELIEF VALVE
This water heater is provided with a properly rated/sized and certified 
combination Temperature-Pressure Relief Valve (T&P relief valve) by 
the manufacturer. The valve is certified by a nationally recognized 
testing laboratory that maintains periodic inspection of production of 
listed equipment of materials as meeting the requirements for Relief 
Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and 
the code requirements of ASME.
If  replaced,  the  new  T&P  valve  must  meet  the  requirements 
of  local  codes,  but  not  less  than  a  combination  Temperature-
Pressure  Relief  Valve  rated/sized  and  certified  as  indicated  in 
the  above  paragraph.  The  new  valve  must  be  marked  with  a 
maximum  set  pressure  not  to  exceed  the  marked  hydrostatic 
working pressure of the water heater (150 psi = 1,035 kPa) and 
a discharge capacity not less than the water heater Btu/hr or kW 
input rate as shown on the water heater’s model rating plate.
NOTE: In addition to the factory installed Temperature-Pressure 
Relief  Valve  on  the  water  heater,  each  remote  storage  tank 
that  may  be  installed  and  piped  to  a  water  heating  appliance 
must  also  have  its  own  properly  sized,  rated  and  approved 
Temperature-Pressure  Relief  Valve  installed.  Call  the  toll  free 
technical  support  phone  number  listed  on  the  back  cover  of 
this  manual  for  technical  assistance  in  sizing  a  Temperature-
Pressure Relief Valve for remote storage tanks.
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22-
CSA 4.4 and ASME code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
For  safe  operation  of  the  water  heater,  the  Temperature-
Pressure Relief Valve must not be removed from its designated 
opening  nor  plugged.  The  Temperature-Pressure  Relief  Valve 
must  be  installed  directly  into  the  fitting  of  the  water  heater 
designed for the relief valve. Install discharge piping so that any 
discharge will exit the pipe within 6 inches (15.2 cm) above an 
adequate floor drain, or external to the building. In cold climates 
it  is  recommended  that  it  be  terminated  at  an  adequate  drain 
inside the building. Be certain that no contact is made with any 
live electrical part. The discharge opening must not be blocked 
or reduced in size under any circumstances. Excessive length, 
over 30 feet (9.14 m), or use of more than four elbows can cause 
restriction and reduce the discharge capacity of the valve.
No  valve  or  other  obstruction  is  to  be  placed  between  the 
Temperature-Pressure Relief Valve and the tank. Do not connect 
discharge piping directly to the drain unless a 6” (15.2 cm) air gap 
is  provided.  To  prevent  bodily  injury,  hazard  to  life,  or  property 
damage,  the  temperature-pressure  relief  valve  must  be  allowed 
to  discharge  water  in  adequate  quantities  should  circumstances 
demand. If the discharge pipe is not connected to a drain or other 
suitable means, the water flow may cause property damage.