POWERED ANODE ROD (OPTIONAL MODELS)
To insure a long, trouble-free operating life, certain models of 
water heaters covered in this manual are factory equipped with 
a  powered  anode  system. The  anode  rod  is  of  a  permanent 
design  and  does  not  need  replacing  unless  damaged. 
Inspection and cleaning should be performed once a year.
NOTE: Follow the instructions to drain the water heater storage 
tank first. Remove the powered anodes from the water heater by 
loosening the 3/4” NPT bushing that forms the top of the anode 
rods. Do not disassemble the retaining nut and wire terminal 
from the top while installed in the water heater, the anode rods 
electrode may fall inside the tank. Remove the entire anode rod 
from the water heater prior to inspection. Clean the anode rods 
with a soft cloth and reinstall. Follow the instructions for filling 
the water heater when finished.
TEMPERATURE-PRESSURE RELIEF VALVE TEST
        
It  is  recommended  that  the  Temperature-Pressure  Relief  Valve 
should be checked to ensure that it is in operating condition every 
6 months.
When  checking  the  Temperature-Pressure  Relief  Valve  operation, 
make  sure  that  (1)  no  one  is  in  front  of  or  around  the  outlet  of  the 
Temperature-Pressure  Relief  Valve  discharge  line,  and  (2)  that  the 
water discharge will not cause any property damage, as the water may 
be extremely hot. Use care when operating valve as the valve may be 
hot.
To check the temperature-pressure relief valve, lift the lever at the end of 
the valve several times, see Figure 37. The valve should seat properly 
and operate freely.
If after manually operating the valve, it fails to completely reset 
and  continues  to  release  water,  immediately  close  the  cold 
water inlet to the water heater and drain the water heater, see 
Draining And Flushing on Page 49. Replace the Temperature-
Pressure Relief Valve with a properly rated/sized new one, see 
Temperature-Pressure Relief Valve on Page 22 for instructions 
on replacement.
DISCHARGE PIPE
TEMPERATURE-PRESSURE
RELIEF VALVE
Figure: 37
If  the  Temperature-Pressure  Relief  Valve  on  the  water  heater 
weeps  or  discharges  periodically,  this  may  be  due  to  thermal 
expansion.
NOTE: Excessive water pressure is the most common cause of 
Temperature-Pressure Relief Valve leakage. Excessive water 
system pressure is most often caused by “thermal expansion” 
in a “closed system.” See Closed Water Systems and Thermal 
Expansion on Page 21. The Temperature-Pressure Relief Valve 
is not intended for the constant relief of thermal expansion.
Temperature-Pressure  Relief  Valve  leakage  due  to  pressure 
build  up  in  a  closed  system  that  does  not  have  a  thermal 
expansion  tank  installed  is  not  covered  under  the  limited 
warranty.  Thermal  expansion  tanks  must  be  installed  on  all 
closed water systems.
DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF 
VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE,  
SERIOUS INJURY OR DEATH.
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22-
CSA 4.4 and ASME code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
DRAINING AND FLUSHING
It is recommended that the water heater storage tank be drained 
and  flushed  every  6  months  to  reduce  sediment  buildup.  The 
water heater should be drained if being shut down during freezing 
GALLON UNIT” Features And Components in this manual for the 
location of the water heater components described below.
Burn harzard.
Hot water discharge.
Keep  hands   clear  of  drain
valve  discharge.
Burn hazard.
Hot water discharge.
Keep clear of Temperature-
Pressure Relief Valve
discharge outlet.