10. INSPECTION 
 
10. INSPECTION 
WARNING 
Before starting maintenance and/or inspection, turn off the power and wait for 15 
minutes or more until the charge lamp turns off. Then, confirm that the voltage 
between P and N is safe with a voltage tester and others. Otherwise, an electric 
shock may occur. In addition, always confirm from the front of the servo amplifier 
whether the charge lamp is off or not. 
Any person who is involved in inspection should be fully competent to do the work. 
Otherwise, you may get an electric shock. For repair and parts replacement, 
contact your safes representative. 
 
POINT 
 
Do not test the servo amplifier with a megger (measure insulation 
resistance), or it may become faulty. 
Do not disassemble and/or repair the equipment on customer side. 
 
(1) Inspection 
It is recommended to make the following checks periodically. 
(a) Check for loose terminal block screws. Retighten any loose screws. 
(b) Check the cables and the like for scratches and cracks. Perform periodic inspection according to 
operating conditions. 
 
(2) Life 
The following parts must be changed periodically as listed below. If any part is found faulty, it must be 
changed immediately even when it has not yet reached the end of its life, which depends on the 
operating method and environmental conditions. For parts replacement, please contact your sales 
representative. 
 
Part name 
Life guideline 
Smoothing capacitor 
10 years 
Relay 
Number of power-on and number of forced 
stop times : 100,000 times 
Cooling fan 
10,000 to 30,000hours (2 to 3 years) 
Servo amplifier 
Absolute position battery 
Refer to section 4.5 
 
(a) Smoothing capacitor 
Affected by ripple currents, etc. and deteriorates in characteristic. The life of the capacitor greatly 
depends on ambient temperature and operating conditions. The capacitor will reach the end of its 
life in 10 years of continuous operation in normal air-conditioned environment. 
 
(b) Relays 
Their contacts will wear due to switching currents and contact faults occur. Relays reach the end of 
their life when the cumulative number of power-on and forced stop times is 100,000, which depends 
on the power supply capacity. 
 
(c) Servo amplifier cooling fan 
The cooling fan bearings reach the end of their life in 10,000 to 30,000 hours. Normally, therefore, 
the cooling fan must be changed in a few years of continuous operation as a guideline. 
It must also be changed if unusual noise or vibration is found during inspection.