DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Alarms, Errors, and Troubleshooting 
5-2
DEFINITY AUDIX System Power Procedures 
5
Before powering down a cabinet or carrier that contains DEFINITY AUDIX 
circuit packs (TN566), first power down the AUDIX unit to avoid damaging 
the AUDIX software. Instructions for powering down this unit are in the 
‘‘DEFINITY AUDIX System Power Procedures’’
 below, on the circuit pack, 
and in DEFINITY AUDIX documentation.
When you are finished working on a cabinet, replace and secure all panels 
and covers to avoid disseminating electromagnetic interference.
DEFINITY AUDIX System Power 
Procedures
Manually Power Down AUDIX System
A yellow caution sticker on the system’s power unit notifies technicians to shut 
down the DEFINITY AUDIX System prior to powering down the system.
1. Using a pointed object, such as a paper clip or pen (do not use a pencil), 
press the Boot/shutdown button. The button is located at the top right 
portion of the front panel.
2. Hold the boot/Shutdown button in until the LCD display flashes the 
message 
MSHUT.
 
3. Release the Boot/Shutdown button.
NOTE:
The DEFINITY AUDIX System takes about five minutes to shut down. 
The “heartbeat” indication on the display continues to flash.
Manually Power Up AUDIX System
1. Using a pointed object such as a paper clip or a pen (do not use a pencil), 
press the Boot/Shutdown button.
2. Hold the boot/Shutdown button in until the display indicates the message, 
BTEST
, steady on.
3. Release the Boot/Shutdown button. the DEFINITY AUDIX system takes 
approximately 5 minutes to power up.
The display has the following sequence of steady on messages:
— OSINIT
— OS
— AINIT
— ADX