GP Series Portable Chillers 
Chapter 6: Troubleshooting 
53 of 90 
system fault 
Chiller too small for load 
Verify with sales representative 
the sizing of the chiller for the 
application. 
Low Condenser Differential 
Pressure Warning 
18 
Low discharge pressure or 
high suction pressure 
Contact customer service 
Condenser Inlet Temp Sensor 
Failure (optional with sensor 
pack) 
19 
Sensor wires loose from 
controller terminal block 
Verify wiring at terminal block.  
Sensor wires broke between 
sensor and controller terminal 
block. 
Replace temperature sensor 
Chiller In Fluid Temp Sensor 
Failure 
20 
Sensor wires loose from 
controller terminal block 
Verify wiring at terminal block.  
Sensor wires broke between 
sensor and controller terminal 
block. 
Replace temperature sensor 
Evaporator Differential Pressure 
21 
Blocked evaporator  
Backflush evaporator  
Blocked Y-strainer 
Blow down y-strainer by 
opening blow-down valve or 
clean internal strainer.  
High Discharge Pressure Warning  22 
Dirty air cooled condenser or 
inlet filter 
Clean filter or condenser 
Dirty water cooled condenser 
or condenser valve failure 
Clean condenser or verify 
operation of condenser valve 
Condenser fan overload 
See Fan Overload Fault 
Condenser fan VFD fault 
See VFD Fault 
Ambient air or condenser 
water temperature too high 
Verify supply temperature or air 
removal capacity. 
Too much refrigerant in 
system. 
Contact Customer Service for 
assistance 
Liquid line valves closed. 
Verify operation of valve and 
wiring on controller 
High Fluid Temp Warning 
23 
Fluid temperature higher than 
parameter. 
Verify parameter and adjust if 
necessary. 
Refrigeration system fault 
Check for any refrigeration 
system fault 
Chiller too small for load 
Verify with sales representative 
the sizing of the chiller for the 
application. 
 
CC = Compressor Critical 
SC = System Critical 
PC = Process Critical  W = Warning 
Alarm Name 
Type  Possible Cause 
Solution 
High Level Fault 
24 
Fluid level higher than 
parameter setting. 
Verify value in parameter 
Too much fluid in system 
Open drain valve and remove 
some fluid from system so that 
level is below high level fault. 
Tank sensor failure 
Replace sensor 
High Level Warning 
25 
Fluid level higher than 
parameter setting. 
Verify value in parameter 
Too much fluid in system 
Open drain valve and remove 
some fluid from system so that 
level is below high level 
warning. 
Tank sensor failure 
Replace sensor 
Compressor Differential Pressure 
Fault 
26 
CC 
Low discharge pressure or 
high suction pressure 
Contact customer service 
High Suction Pressure Warning 
27 
From Process fluid 
temperature too high 
Verify flow through system.  
Make corrections as necessary. 
Low Discharge Pressure Warning 
28 
Ambient air or condenser 
Verify ambient air temperature