GP Series Portable Chillers 
Chapter 6: Troubleshooting 
54 of 90 
water temperature too low 
and air flow or condenser inlet 
water temperature.   
Too little refrigerant in 
system. 
Contact customer service for 
service call 
Water cooled condenser valve 
stuck open 
Verify cooling valve operation. 
Fan VFD output at 100% 
Verify VFD is in remote versus 
manual operation.  Verify 
controller output to VFD. 
Low Fluid Temp Warning 
29 
 
 
Low Level Warning 
30 
Fluid level lower than 
parameter setting. 
Verify value in parameter. Add 
fluid to the system if necessary 
Optional Water Makeup valve 
failure 
Verify wiring between 
controller and makeup valve.  
Replace valve if necessary 
Tank sensor failure 
Replace sensor 
Compressor Differential Pressure 
Warning 
31 
Low discharge pressure or 
high suction pressure 
Contact customer service 
Low Suction Pressure Warning 
32 
System low on refrigerant 
Contact Customer Service 
Liquid line valves closed 
Verify wiring or output between 
controller and valve 
Chilled fluid setpoint too 
close to freeze protection 
setpoint. 
Adjust setpoint or fluid 
freezepoint temperature (will 
require adding glycol to fluid) 
Process fluid flow rate too 
low. 
Verify system valve operation 
and adjust if necessary 
Thermal expansion valve 
failure. 
Contact Customer Service 
Pump Down Override Time 
Expired 
33 
Liquid line valve open 
Contact customer service 
Hot gas bypass valve open 
 
 
CC = Compressor Critical 
SC = System Critical 
PC = Process Critical  W = Warning 
Alarm Name 
Type  Possible Cause 
Solution 
Pump Flow Sensor Failure 
34 
Optional flow sensor failed 
Verify wiring of flow sensor at 
sensor and terminal block of 
controller 
Pump Pressure Sensor Failure 
35 
Sensor wires loose from 
controller terminal block 
Verify wiring of sensor at 
sensor and terminal block of 
controller 
Sensor wires broke between 
sensor and controller terminal 
block. 
Refrig Liquid Temp Sensor 
Failure 
36 
Sensor wires loose from 
controller terminal block 
Verify wiring of sensor at 
sensor and terminal block of 
controller 
Sensor wires broke between 
sensor and controller terminal 
block. 
Refrig Suction Temp Sensor 
Failure 
37 
Sensor wires loose from 
controller terminal block 
Verify wiring of sensor at 
sensor and terminal block of 
controller 
Sensor wires broke between 
sensor and controller terminal 
block. 
Tank Level Sensor Failure 
38 
Sensor wires loose from 
controller terminal block 
Verify wiring of sensor at 
sensor and terminal block of 
controller 
Sensor wires broke between 
sensor and controller terminal 
block. 
Water make-up failure 
40 
Make up solenoid failure 
Verify wiring of solenoid valve 
at valve and at terminal block. 
Insufficient water pressure 
Increase water pressure to be 
above 5 psig (0.3 bar)