6.
 
CONNECTION OF REMOTE I/O UNIT 
6.6  Outline of Digital Signal Output Circuit 
 
 
I - 
61
 
6.6  Outline of Digital Signal Output Circuit 
 
The digital signal output circuit uses a sink type (DX1
†0) or source type (DX1†1). 
Use within the specification ranges shown below. 
 
Output circuit 
 
 
R
(Machine side)
Control 
circuit 
24VDC(+) 
Sink type (DX1†0) 
RA
PL
DO-L/DO-R 
R
Source (DX1†1) 
RA
PL
24VDC(+)
DO-L/DO-R 
(Machine side)
Control 
circuit 
 
 
 
 
Output conditions 
Insulation method 
Non-insulation 
Rated load voltage 
24VDC 
Max. output current 
60mA 
Output delay time 
40µs 
 
 
When using an inductive load such as a relay, always connect a diode (voltage 
resistance 100V or more, 100mA or more) in parallel to the load. 
When using a capacity load such as a lamp, always connect a protective resistor (R=150
Ω) 
serially to the load to suppress rush currents. (Make sure that the current is less than the above 
tolerable current including the instantaneous current.) 
<CAUTION
 
 
 CAUTION 
 
 
When using an inductive load such as relays, always connect a diode in parallel to the 
load as a noise countermeasure. 
 
When using a capacitive load such as a lamp, always connect a protective resistor in 
series to the load to suppress rush currents.