Справочник Пользователя для Omni Group GREEN SMART 864

Скачать
Страница из 72
 
Installation
  
(for qualified installers only)
 
11 
© Travis Industries 
4090507 
100-01217_000 
Fireplace Placement Requirements 
•  Fireplace must be installed on a level surface capable of supporting the fireplace and vent. 
•  Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet). 
•  This heater may be placed in a bedroom.  Please be aware of the large amount of heat this appliance 
produces when determining a location. 
•  Fireplace must be installed in a room with a minimum ceiling height of 84” (2134mm). 
Clearances 
•  The fireplace requires a ½” (13mm) clearance from the left side of the fireplace to the framing members.  No 
material (insulation, framing, etc.) may be placed into this area. 
0" (0mm) clearance on 
right side of fireplace.  
NOTE: right side 
standoff is optional.
1/2" (13mm) 
Clearnce on left 
side of 
fireplace.
 
•  When installed, walls in front of the fireplace must be a minimum 1" (25mm) to the side of the fireplace.  Only 
one side wall is allowed within 12” (305mm) of the side of the fireplace. 
•  Due to the high temperature, the heater should be located out of traffic and away from furniture and 
draperies. 
•  Fireplace must be placed so the vents below and above the glass do not become blocked. 
Raised Fireplaces 
•  The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace (310 Lbs. 
140.7 Kg) and vent.   
Platform
Optional Raised  Hearth
 (see "Hearth Requirements" for details)
Min. 42" (1067mm) 
Fireplace Enclosure
Height