12 Installation 
 
(for qualified installers only)
 
© Travis Industries 
4090507 
100-01217_000 
Minimum Framing Dimensions – Top or Side Vent Configuration 
* The 23" (584mm) dimension is based upon 1/2" (13mm) 
drywall around the perimeter of the fireplace on both sides.  If 
using thicker drywall (or other facing), you will need to adjust this 
dimension.
44"
1118mm
Minimum 42”(1067mm) 
Fireplace Enclosure Height
NOTE:
The shaded framing must be 
installed  after placing the fireplace 
in position.
The framing above the fireplace 
interferes with the top of the fireplace.  
If using the side vent configuration, do 
not install the framing to the left side 
(shown in light gray).
38-1/2"
978mm
23" *
584mm
Back
Front
Right
Left