MT2000-0200-1 Rev f (10-2007) 
DCN0160
                                                                                                                       17
 
4.5.5   
Bench Calibration of the 4mA & 20mA Points: 
 
After the transmitter is configured correctly, a manual bench calibration of the 4mA and 20mA points using hands or 
targets, can be done as follows. 
 
Note: The following applies to single or dual Rod and Cable probes only. Other assemblies such as coaxial probes 
must be calibrated with products. 
 
If the probe is a rod, position it so that it stands clear of any objects (minimum of 6 in. / 152 mm).  For support use 
only very low dielectric materials (such as Styrofoam blocks).  If the probe is a cable hang the cable vertically in 
open space or place it under tension between the coupler and cable end.  An open palm of the hand or a metal plate 
can be used as a target if placed perpendicular to the probe.  Use the front of the hand as the measuring surface, 
and place rod between two middle fingers. A suitable metal target can be a 6 in. / 152 mm diameter plate with a slot 
or hole in the center, to slide over the sensing rod. This method will simulate high dielectric product such as water. 
 
•  Setting the 4mA point: 
•  Enter the calibration mode by pressing the UP & DOWN buttons together for 3 seconds. 
•  Place hand or target at 0% level and press the DOWN button for 1 second to set the output at  
  
4.00mA. 
 
•  Setting the 20mA point: 
•  Enter the calibration mode by pressing the UP & DOWN buttons together for 3 seconds. 
•  Place hand or target at 100% level and press the UP button for 1 second to set the output at   20.00mA. 
Note:  The above steps can be repeated as many times as required.  The easiest way to set the 4 mA and 20 mA 
points is through the CAL menu as described in Section 4.3. 
  
4.5.6  4mA & 20mA Calibration Using Actual Level Input: 
  
A manual calibration of the 4mA and 20mA points using the actual vessel level can be done as follows: 
 
•  Setting the 4mA point: 
•  Enter the calibration mode by pressing the UP & DOWN buttons together for 3 seconds. 
•  Establish a tank level of 0% and press the DOWN button for 1 second to set the output at 4.00mA. 
 
•  Setting the 20mA point: 
•  Enter the calibration mode by pressing the UP & DOWN buttons together for 3 seconds. 
•  Establish a tank level of 100% and press the UP button for 1 second to set the output at 20.00mA. 
 
Notes:  The above steps can be repeated as many times as required. 
 
•  Should CALIBRATE be entered inadvertently, pressing SELECT will exit this function, making no changes to 
LRV or URV.