OFF-RATIO WARNING & ALARM  SETTINGS
 
 
 
Since the EMO 500 is primarily a Ratio Monitor, Limits 1 and 2 are factory set to be 
triggered by an off-ratio condition.  
 
 Default values are set at Limit 1 = Warning 5% and Limit 2 = Alarm 10%. 
 
For example: If the RATIO WARNING is programmed at +/- 10%, then the LIMIT 1 
contact will close when this event occurs. LIMIT 2 will be similarly activated by the 
value programmed in the RATIO ALARM. Note - Press key #5 to review the current 
ratio alarm settings and key #9 to review the limit status. Off-ratio alarms can be reset 
easily by pressing either F3 (Reset A) or F4  (Reset B).