APC Smart-UPS
®
VT ISX Enclosure
30-40 kVA 400 V for 5 Battery Modules
with Power Distribution Unit (PDU)
Installation
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Rear
Front
LOAD ON
LOAD ON
ON-BATTTT
BYP
BYPASS
ASS
FAUL
AULT
ESC
ESC
?
Warning
Always read the separate Safety Sheet 990-2822 prior to the
installation.
installation.
Warning
All electrical power and power control wiring must be installed by
a qualified electrician, and must comply with local and national
regulations for maximum power rating.
a qualified electrician, and must comply with local and national
regulations for maximum power rating.
Warning
The UPS must be supplied from a 380 Y/220 V 4 W + GND 50/60
Hz or 400 Y/230 V 4 W 50/60 Hz or 415 Y/240 V 4 W + GND 50/60
Hz source.
Hz or 400 Y/230 V 4 W 50/60 Hz or 415 Y/240 V 4 W + GND 50/60
Hz source.
Note
Power terminal lug diameter: minimum 6 mm. Torque value: 7 Nm.
1
Cable Entry
Cable entry takes place from the rear of the UPS. Pull out the lower end of
the handle and turn it counterclockwise to a horizontal position to open
the door.
the handle and turn it counterclockwise to a horizontal position to open
the door.
Preparing for cabling (general)
Use a torx screwdriver to loosen the 12 M4 screws from the cable
landing covers and remove the screws.
landing covers and remove the screws.
Cut crosses for cable
access in the required
number of the blanking
plugs (top or bottom as
required). Line the holes
with grommets.
access in the required
number of the blanking
plugs (top or bottom as
required). Line the holes
with grommets.
Bottom cable entry
Remove the two M4
screws from the bottom
plate and remove the
plate.
plate and remove the
plate.
Punch holes in bottom
plate for cables as required. Line hole(s) with grommets.
Reinstall the plate.
Reinstall the plate.
Note
Make sure that the UPS is in its location of use before you
start the cabling.
start the cabling.
Rear view of
UPS
(for external
batteries)
Rear view of
UPS
(for internal
batteries)
Power
Module
with cable
landings
Module
with cable
landings
PDU
Power
Module
with cable
landings
Module
with cable
landings
PDU
Bottom entry
Top entry
Smart-UPS® VT ISX, 30-40 kVA, 400V, Installation Sheet
Guide cable
through the bottom
holes.
holes.
Feed cables
through the
blanking plugs into
the cable landing
area.
blanking plugs into
the cable landing
area.
Attach cables to
the slotted plate
using cable ties
(not supplied).
using cable ties
(not supplied).
Top cable entry
.
From the rear of the inside of the UPS push the spring locks on the
top cover backwards and lift up the rear end of top plate.
top cover backwards and lift up the rear end of top plate.
Slide out the top plate (mind the wing on either side of the plate).
Punch hole(s) in the labeled area between the two rails on the rear of
the top cover for cables as required. Line the hole(s) with grommets.
Reinstall the top plate.
the top cover for cables as required. Line the hole(s) with grommets.
Reinstall the top plate.
Feed the cables
through the
punched holes in
the top cover, and
guide the cables
into the cable
landing area.
punched holes in
the top cover, and
guide the cables
into the cable
landing area.
Attach the cable to
the side panel with
cable ties (not
supplied).
cable ties (not
supplied).
AC input
Bypass/
battery
cables
Rear
Front
Bypass/
battery
cables
AC input