APC SUVTR40KH5B5S 用户手册

下载
页码 4
990-2813C
08/2006
*990-2813C*
APC Smart-UPS
®
 VT ISX Enclosure
30-40 kVA 400 V for 5 Battery Modules 
with Power Distribution Unit (PDU)
Installation
IMPORTANT SAFETY INSTRUCTIONS 
SAVE THESE INSTRUCTIONS
Rear
Front
LOAD ON
LOAD ON
ON-BATTTT
BYP
BYPASS
ASS
FAUL
AULT
ESC
ESC
?
Warning
Always read the separate Safety Sheet 990-2822 prior to the 
installation.
Warning
All electrical power and power control wiring must be installed by 
a qualified electrician, and must comply with local and national 
regulations for maximum power rating
.
Warning
The UPS must be supplied from a 380 Y/220 V 4 W + GND 50/60 
Hz or 400 Y/230 V 4 W 50/60 Hz or 415 Y/240 V 4 W + GND 50/60 
Hz source.
Note
Power terminal lug diameter: minimum 6 mm. Torque value: 7 Nm.
1
Cable Entry
Cable entry takes place from the rear of the UPS. Pull out the lower end of 
the handle and turn it counterclockwise to a horizontal position to open 
the door.
Preparing for cabling (general)
Use a torx screwdriver to loosen the 12 M4 screws from the cable 
landing covers and remove the screws.
Cut crosses for cable 
access in the required 
number of the blanking 
plugs (top or bottom as 
required). Line the holes 
with grommets.
Bottom cable entry
Remove the two M4 
screws from the bottom 
plate and remove the 
plate.
Punch holes in bottom 
plate for cables as required. Line hole(s) with grommets.
Reinstall the plate.
Note
Make sure that the UPS is in its location of use before you 
start the cabling.
Rear view of 
UPS
(for external 
batteries)
Rear view of 
UPS
(for internal 
batteries)
Power 
Module 
with cable 
landings
PDU
Power 
Module 
with cable 
landings
PDU
Bottom entry
Top entry
Smart-UPS® VT ISX, 30-40 kVA, 400V, Installation Sheet
Guide cable 
through the bottom 
holes.
Feed cables 
through the 
blanking plugs into 
the cable landing 
area.
Attach cables to 
the slotted plate 
using cable ties 
(not supplied).
Top cable entry
.
From the rear of the inside of the UPS push the spring locks on the 
top cover backwards and lift up the rear end of top plate.
Slide out the top plate (mind the wing on either side of the plate).
Punch hole(s) in the labeled area between the two rails on the rear of 
the top cover for cables as required. Line the hole(s) with grommets. 
Reinstall the top plate.
Feed the cables 
through the 
punched holes in 
the top cover, and 
guide the cables 
into the cable 
landing area.
Attach the cable to 
the side panel with 
cable ties (not 
supplied).