Table 4   - 
 
Required Clearances
Unit
Combustible 
Clearance
Accessibility, 
Cleaning, and 
Servicing 
Top
1”  (26mm)
8” (204mm)
Left Side
1 “ (26mm)
24” (610mm)
Right Side
11” (280mm)
-
Base
1”  (26mm)
-
Front
1”  (26mm)
24” (610mm)
Back
1”  (26mm)
-
Intake/Vent Piping
0  (0)
-
Near Boiler Hot         
Water Piping
1”  (26mm)
-
All distances measured from the cabinet of the boiler.
Locating The Boiler
1. 
Place crated boiler as close to selected location as 
possible and un-crate boiler. Boiler may be moved into 
position with appliance dolly or 2 wheel hand truck. 
Insert dolly or hand truck under left hand side of 
boiler. It is possible to slide boiler for short distance on 
smooth fl oor or surface.
1. 
Select level location central to piping systems served 
and as close to vent and air intake terminals as 
possible.
2. 
Accessibility clearances, if more stringent (i.e. larger 
clearances) than required fi re protection clearances, 
must be used for boiler installation. Accessibility 
clearances may be achieved with the use of removable 
walls or partitions.
3. 
Boiler is approved for installation in closets and on 
combustible fl oors. This boiler shall NOT be installed on 
carpeting.
4. 
Clearances shown in  Table 4 
 
indicate required 
clearances. Maintain minimum 1” clearance between 
combustible construction and each of left, top and 
back surfaces of the boiler. Minimum 11” clearance 
is required on right side, to allow room for induced 
draft blower. Maintain 18” clearance at side where 
passage is required to access another side for cleaning 
or servicing, inspection or replacement of parts.  Allow 
24” at front and left side and 8” at top for servicing. No 
clearances are required to venting or combustion air 
intake piping.
5. 
Install equipment in location which facilitates operation 
of venting and combustion air intake piping systems as 
described in this manual.
6. 
Advise owner to keep venting and combustion air 
intake passages free of obstructions. Both venting 
and combustion air intake piping systems connected 
to outdoors must permit fl ow through piping systems 
without restrictions for boiler operation.
7. 
Install boiler such that the automatic gas ignition 
system components are protected from water 
(dripping, spraying, rain, etc.) during operation and 
service (circulator replacement, condensate trap, 
control replacement, etc.).
Combustion Air And Vent Pipe Requirements
This boiler requires a dedicated direct vent system. In a 
direct vent system, all air for combustion is taken directly 
from outside atmosphere, and all fl ue products are 
discharged to outside atmosphere.
Terminate combustion air and vent pipe connections in 
same atmospheric pressure zone, through roof or sidewall 
(roof termination preferred). See
 
 
Figure 12
  thru  Figure 14 , 
pages 24 and 25 for required clearances.
• Keep boiler area clean of debris and free of fl ammable 
and combustible materials, vapors and liquids.
• When vent pipe is exposed to temperatures below 
freezing, such as when it passes through an unheated 
space or when chimney is used as a raceway, vent pipe 
must be insulated with 1/2” Armafl ex or equivalent. 
In extreme cold climate areas, use ¾” Armafl ex or 
equivalent.
 WARNING
Solvent cements are combustible. Keep away from 
heat, sparks, and open fl ame. Use only in well ven-
tilated areas. Avoid breathing in vapor or allowing 
contact with skin or eyes. Failure these instructions 
could result in fi re, personal injury, or death.
!
  
• Combustion air must be clean outdoor air. Combustion 
air must not be taken from inside structure because 
that air frequently is contaminated by halogens, which 
include fl uorides, chlorides, phosphates, bromides and 
iodides. These elements are found in aerosols, deter-
gents, bleaches, cleaning solvents, salts, air fresheners, 
paints, adhesives and other household products.
• Locate combustion air inlet as far away as possible 
from swimming pool and swimming pool pump house.
• All combustion air and vent pipes must be airtight and 
watertight. Combustion air and vent piping must also 
terminate as shown in “Combustion Air and Vent 
Pipe” section.
• Vent connections serving appliances vented by 
natural draft shall not be connected into any portion 
of mechanical draft systems operating under positive 
pressure.
BOILER INSTALLATION