VENTILATION & COMBUSTION AIR
Provide combustion air and ventilation air in accordance 
with the section “Air for Combustion and Ventilation,” of the 
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Sections 
8.2, 8.3 or 8.4 of Natural Gas and Propane Installation 
Code, CAN/CSA B149.1, or applicable provisions of local 
building codes.
Provide make-up air where exhaust fans, clothes dryers, 
and kitchen ventilation equipment interfere with proper 
operation.
National Fuel Gas Code recognizes several methods 
of obtaining adequate ventilation and combustion air.  
Requirements of the authority having jurisdiction may 
override these methods.
• Engineered Installations. Must be approved by 
authority having jurisdictions.
• Mechanical Air Supply.  Provide minimum of 0.35 
cfm per Mbh for all appliances located within space.  
Additional requirements where exhaust fans installed.  
Interlock each appliance to mechanical air supply 
system to prevent main burner operation when 
mechanical air supply system not operating.
• All Indoor Air.  Calculate minimum volume for all 
appliances in space.  Use a different method if 
minimum volume not available.
 
о Standard Method. Cannot be used if known air 
infi ltration rate is less than 0.40 air changes per 
hour.  See Table 3 for space with boiler only.  Use 
equation for multiple appliances.
Volume ≥ 50 ft
3
 x Total Input [Mbh]
 
о Known Air Infi ltration Rate.  See Table 3 for 
space with boiler only.  Use equation for multiple 
appliances.  Do not use an air infi ltration rate 
(ACH) greater than 0.60.
Volume ≥ 15 ft
3
/ACH x Total Input [Mbh]
 
о Refer to National Fuel Gas Code for opening 
requirements between connection indoor spaces.
• All Outdoor Air.  Provide permanent opening(s) 
communicating directly or by ducts with outdoors.
 
о Two Permanent Opening Method.  Provide opening 
commencing within 12 inches of top and second 
opening commencing within 12 inches of bottom 
enclosure.
 
 Direct communication with outdoors or 
communicating through vertical ducts.  Provide 
minimum free area of 1 in
2
 per 4 Mbh of total 
input rating of all appliances in enclosure.
 
 Communicating through horizontal ducts.  
Provide minimum free area of 1 in
2
 per 2 
Mbh of total input rating of all appliances in 
enclosure.
 
о One Permanent Opening Method.  Provide opening 
commencing within 12 inches of top of enclosure.  
Provide minimum clearance of 1 inch on sides 
and back and 6 inches on front of boiler (does not 
supersede clearance to combustible materials).
 
о Combination Indoor and Outdoor Air.  Refer to 
National Fuel Gas Code for additional requirements 
for louvers, grilles, screens and air ducts.
• Combination Indoor and Outdoor Air.  Refer to 
National Fuel Gas Code for application information.
National Gas and Propane Installation Code Requires 
providing air supply in accordance with:
• Section 8.2 and 8.3 when combination of appliances 
has a total input of up to and including 400 Mbh (120 
kW).
 
о Does not have draft control device.
• Section 8.4 when combination of appliances has total 
input exceeding 400 Mbh (120 kW).
• Refer to Natural Gas and Propane Installation Code 
for specifi c air supply requirements for enclosure 
or structure where boiler is installed, including air 
supply openings and ducts.
    Table 3- Air Infi ltration Rate
Input Mbh
Standard 
Method
Known Air Infi ltration Rate Method (Air Changes Per Hour)
0.1
0.2
0.3
0.4
0.5
0.6
42.5
2125
6375
3188
2125
1594
1275
1063
75
3750
11250
5625
3750
2813
2250
1875
112.5
5625
16875
8438
5625
4219
3375
2813
150
7500
22500
11250
7500
5625
4500
3750
187.5
9375
28125
14063
9375
7031
5625
4688
225
11250
33750
16875
11250
8438
6750
5625