Справочник Пользователя для MGE UPS Systems 18/280 kVA
MGE UPS SYSTEMS
CleanWave - Installation and user manual Page
5/13
Version 2.1.4 – 15/01/2007 -
2.2. R
ANGE
The following table summarises the characteristics of the different products of the range (at 400V,
50/60Hz).
Minimum sections
1
TYPE Power.
I
phase
max
I
neutral
Max
Total
losses
max
Phases
Neutral (N)
Earth (PE)
( PEN
2
)
[kVA]
[A] [A] [W] [mm²] [mm²] [mm²] [mm²]
CleanWave-18 18 24 43 219 4
10
4
10
CleanWave-30 30 40 72 359 10
25
10
25
CleanWave-40
40
56
101
452
16 35 16 35
CleanWave-55
55
80
144
538 25 2x
25 16 2x
25
CleanWave-90 90 128 231 616 50
2x
50
25
2x
50
CleanWave-140 140 201 361 972 95
2x
95
50
2x
95
CleanWave-180 180 264 476 1212 150 2x
150 95 2x
150
CleanWave-220
220
321
577
1565
2x 95
2x 185
95
2x 185
CleanWave-280
280
401
722
1568
2x 95
2x 240
95
2x 240
Table 4
1
According to European standards
2
If common conductor for neutral and earth (PEN conductor)