2.3. T
ECHNICAL SPECIFICATIONS
 
 
Standards  
 
Construction and safety :  
 
IEC-60439-1 
 
Conception 
 
   IEC-60289, 
IEC-60727
 
 
IP rating 
 
Unprotected 
   IP00 
Protected 
   IP21 
 
Electrical specifications 
 Frequency 
   50 
60Hz 
Nominal voltage between phases : 
400V +15% / -10% 
Reduction ratio  
I
I
Neutral upstream
Neutral downstream
  
1:10 
 
Ratio   
I
I
Neutral
Phase
 : 
 
 
≤ 1.8 
Inrush current :  
 
 
≤ I
nominal 
Overload capacity : 
 
 
10% - 1 hour 
     25% 
10 
minutes 
     50% 
minutes 
Insulation class : 
 
 
1.1 kV 
Dielectric strength : 
 
 
3 kV 
Thermal class of insulation: 
 
 
 
Environmental conditions 
 Maximum ambient temperature : 
50°C 
Maximum altitude : 
 
 
1000m 
Maximum relative humidity : 
 
90% without condensation 
 
 
 
 
 
Please contact your MGE UPS SYSTEMS correspondent for different operating conditions.  
→ 