Series 100 Plus Option Board Analog Output switch settings
Section 3: Installation
Reference, Installation, and Operations Manual
June 2013
3-9000-743 Rev S
3.5.6
Series 100 Plus Option Board Analog Output switch settings
The Series 100 Plus Option Board provides two 4-20 mA analog output signals that are hardware
configurable to either sink or source current as described in
configurable to either sink or source current as described in
and
below
and in Daniel drawing DE-21056 (
).
Full HART® functionality is provided so that any commercially available HART® transmitter
which meets the specifications of the HART® Communications Foundation can be connected to
the Daniel® Ultrasonic Gas Flow Meter.
which meets the specifications of the HART® Communications Foundation can be connected to
the Daniel® Ultrasonic Gas Flow Meter.
Table 3-42 Series 100 Plus Option board Analog In 2 pressure source setting
Board
Switch
Position
Series 100 Plus Option Board
S13-1
SRC
S13-2
SRC
S13-3
SRC
Table 3-43 Series 100 Plus Option Board Analog Out 1 sink settings
Board
Switch
Position
Series 100 Plus Option Board
S14-1
SINK
S14-2
SINK
S14-3
SINK
If the analog output is configured for ‘source’ mode (i.e., powered by the meter), then it
must be at the bottom of the loop (stack). The HART® output cannot be multi-dropped
when configured for source mode.
must be at the bottom of the loop (stack). The HART® output cannot be multi-dropped
when configured for source mode.