 204
Mass rate and totals
Section 6: Meter operation
 Reference, Installation, and Operations Manual
June 2013
3-9000-743 Rev S
The energy rate validity is indicated by the 
EnergyRateValidity data point TRUE(1) indicates 
valid). The energy rate is valid if the base-condition volumetric flow rate is valid (indicated by 
QBaseValidity where TRUE(1) indicates valid) and if the in-use gas properties are valid 
(indicated by 
AreGasPropertiesInvalidInUse where FALSE(0) indicates valid).
The energy rate is accumulated into the corresponding direction energy total regardless of the 
energy rate validity.
The forward and reverse direction energy totals are each stored in non-volatile memory as a 
data pair: a 64-bit unsigned integer portion and a 32-bit floating point fractional portion. For 
example, an energy total of 12345.750 MJ is stored as 12345 MJ for the integer portion and 
0.750 MJ as the fractional portion. Note that while the energy rate can be positive (indicating 
forward flow) or negative (indicating reverse flow), the energy totals are always positive values.
The non-volatile energy total data points are as listed in the table below:
6.1.13
 Mass rate and totals
The Daniel Mark III Ultrasonic Gas Flow Meter meter calculates the mass rate and mass totals 
(forward and reverse). These calculations requires that the flow-condition pressure and 
temperature are available (either fixed or optional analog inputs, 
composition is available (either fixed or optionally read from a GC, 
), and the 
AGA8 calculations are performed (internally by the meter or externally with the results written 
to the meter, 
).
The mass rate is calculated as shown in 
Equation 6-22  Mass rate
where
The sign of the mass rate indicates the flow direction: a positive value indicates flow in the 
forward direction, a negative value indicates flow in the reverse direction.
Table 6-4  Energy total data points
Forward direction
Reverse direction
Integer
Fraction
Integer
Fraction
PosEnergy
PosEnergyFrac
NegEnergy
NegEnergyFrac
=
mass rate (kg/h) (
MassRate)
=
flow-condition volumetric flow rate (m
3
/h) (
QFlow)
=
“in-use” flow-condition gas mass density (kg/m
3
(
RhoMixFlow)
MassRate
Q
Flow
ρ
Flow
×
=
MassRate
Q
Flow
ρ
Flow