Справочник Пользователя для Therma-Stor Products Group D385

Скачать
Страница из 7
4
www.usephoenix.com • sales@thermastor.com
Toll-Free 1-800-533-7533
2.4 Location
Note the following precautions when locating the Phoenix 
D385:
•  It is designed to be used INDOORS ONLY.
•  If used on a water loss work site, plug it into gROUND 
FaULT cIRcUIT INTeRRUPT (gFcI) OUTLeTS
•  The air inlet on top and the side outlet must be at least  
 foot from walls and other air flow obstructions.
•  If the humid area is very large, dehumidification can be 
improved by adding an outlet duct to circulate process 
air to stagnant areas. 
•  DO NOT use the Phoenix D385 as a bench or table.
2.5 Electrical Requirements
When used on a water loss work site, ground fault circuit 
interrupter (GFCI) outlets are required.
Your Phoenix D385 requires a total of 22 amps, 5VAC. 
In order to run at all, this machine must be plugged into 
two separate circuits each with a minimum of  amps 
dedicated capacity available. 
The D385 has two separate power cords, each cord must 
be plugged into its own 5 amp circuit. If both cords are 
plugged into the same 5 amp circuit this circuit will trip 
when the unit is turned on.
Another situation to avoid is that one or both of the 
circuits which the D385 is using can be tripped by other 
appliances drawing power from either circuit. This can 
happen well after a job site has been set-up as in the case 
with a freezer compressor turning on.
Care must be taken to insure that the D385 always has 
sufficient power available to run without tripping breakers 
or blowing fuses.
If your location requires the use of an extension cord, use 
safe techniques in selection and connection. Such cords 
must be grounded and rated for carrying  amps: 4 
gauge minimum for one extension less than 25ft in length 
or 2 gauge for one extension less than 50ft in length.
2.6 Control Panel
2.6A Power Switch
The D385 has one control device, the power switch. 
When the power switch is moved to the “on” position your 
portable desiccant is dehumidifying. The machine will 
continue to dehumidify in all conditions until the power is 
turned off: There is no dehumidistat (see over-dry warning 
section 2.2).
2.6B Pilot Light
The power indicator lamp illuminates to indicate that the 
D385 is functioning properly. This indicator is helpful when 
a job site is too noisy to know what equipment is running 
properly. At a glance from across the room the operator 
can verify that the D385 is operating as it should.
2.6C Hour Meter
The hour meter will run whenever your D385 is on. 
This digital hour meter measures the cumulative time 
of operation in one-tenth hour increments. This non-
resettable time is often used to verify hours on a job or 
to schedule maintenance. When the D385 is un-plugged 
the timer will continue to hold and display the cumulative 
hours run.
2.7 Ducting Connections
Using excess duct length significantly reduces air flow 
volume through duct. This is true in any application. If the 
job at hand needs a short length of duct, cut a section to 
the appropriate length. If air flow is restricted by excess 
length, performance will suffer. The same can be said of 
excess bends in the ducting.
Three different duct sizes are used on the D385. All 
ducting materials are available from Therma-Stor LLC (see 
accessories list section ).
Process in: 12” flex duct.
To attach flex duct to the process air intake, push the wire 
of the first couple of loops down below the four tabs in the 
top cover.
Process out: 10” diameter lay flat plastic duct. 
When inflated this ducting forms a 0” circle. 0” lay flat 
ducting attaches to the D385 by means of a 2”x 6” wire 
rectangle. To attach lay flat ducting to the process exhaust 
air (Fig. , P3), put the plastic duct end through the collar 
center and roll the plastic ducting’s end outward so that 
it overlaps the outside of the collar. The duct and collar 
quickly attach to the D385 by snapping over the four screw 
posts surrounding the process air exhaust (Fig. , P3).
Reactivation in & out: 6” flex duct.
Both reactivation air streams use the same type of duct 
connections.
The 6” flex ducting connections on the D385 consist 
of a detachable 6” starting collar. Slide 6” flex ducting 
over the starting collar and zip-tie or duct tape in place. 
To remove the starting collar (and its attached ducting 
length) depress the snap button and rotate the duct collar 
5° clockwise. After rotating pull the duct collar straight 
out from the cabinet. Flex duct and collar may be stored 
beneath top cover.