Programmable Outputs 
EN | 74 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
2,7 Fire 
Alarm 
Verification 
This feature is used on some commercial fire control 
panels to reduce false alarms from smoke detectors. 
It is similar to zone pulse count used in some motion 
detectors. A fire zone is allotted a pulse count of 3 
pulses over a period of 3 min. 
If the smoke detector trips, the voltage to the smoke 
detector is disconnected for 15 sec and then 
reapplied. No alarm is registered. 
If the unit activates again within 3 min of the first 
activation, no alarm is registered and the voltage to 
the smoke detector is again disconnected for 15 sec 
and then reapplied. 
If a third activation is detected within 3 min of the 
first activation, (three pulses in 3 min) a fire alarm is 
registered. Power to the smoke detector is maintained 
to facilitate unit identification through the detector 
memory. 
Connect this output to the negative side of any 
fire/smoke detector. To configure an output for this 
feature, use these settings. 
EVENT TYPE – 2,7 
POLARITY – 10 
TIMEBASE – 2 
MULTIPLIER – 15 
The zone to which the fire or smoke detector is 
connected should be programmed as: 
ZONE TYPE – 13 
ZONE PULSE COUNT – 3 
ZONE PULSE COUNT TIME – 15 
2,8 Remote 
Control 
2,9 Remote 
Control 
2,10 Remote 
Control 
These outputs can be remotely activated (turned on 
or off) by the following methods: 
•  Remote codepad (refer to Section 5.2.7 Turning 
Outputs On/Off for more information). 
•  Remotely through the Alarm Link Software 
(refer to your Alarm Link Instruction Manual for 
further information). 
2,11 
Radio Control Output 1 
This output operates when the [DOOR] button on 
the 4-channel hand-held transmitter is activated when 
the system is armed or disarmed. 
2,12 
Radio Control Output 2 
This output operates when the [AUX] button on the 
4-channel hand-held transmitter is activated when the 
system is armed or disarmed.  
If you select Option 8 in Location 492 (refer to 
Section 18.1 System Options 1 on page 80), this output 
does not operate and arms the system in STAY 
Mode 1 only. 
2,13 
Radio Control Output 1 – Not in AWAY 
Mode 
This output operates when the [DOOR] button on 
the 4-channel hand-held transmitter is activated when 
the system is disarmed or armed in STAY Mode 1 or 
STAY Mode 2. The output does not operate when 
the system is armed in AWAY Mode. 
2,14 
Radio Control Output 2 – Not in AWAY 
Mode 
This output operates when the [AUX] button on the 
4-channel hand-held transmitter is activated when the 
system is disarmed or armed in STAY Mode 1 or 
STAY Mode 2. The output does not operate when 
the system is armed in AWAY Mode. 
If you select Option 8 in Location 492 (refer to 
Section 18.1 System Options 1 on page 80), this output 
does not operate and arms the system in STAY 
Mode 1 only. 
2,15 
Communications Failure after Three 
Unsuccessful Calls 
This output operates after the communication dialer 
makes three unsuccessful calls to the base station 
receiver. The output is reset when all messages are 
transmitted (that is, when the buffer is empty or when 
all possible attempts are made). 
3,0 Communications 
Failure 
This output operates after the communication dialer 
makes all possible attempts to reach the base station 
receiver. The output is reset when the first Kiss-Off is 
received. This output does not operate for domestic 
formats. 
3,1 Dialer 
Disabled 
This output operates when the Dialer reporting 
functions allowed option (1) in Location 177 is not 
selected (refer to Section 12.1 Dialer Options 1 on page 
52). The output is reset when Option 1 is selected. 
3,2 Dialer 
Active 
This output operates when the communication dialer 
is online. The output is reset when the 
communication dialer releases the telephone line. 
3,3 Ring 
Detect 
This output operates when an incoming call is 
detected by the control panel. The output is reset 
when the ringing stops or when the call is answered. 
3,4 
Codepad Panic (Multi-Break)  
This output operates when a Panic Alarm is initiated 
from the codepad. The output operates for 200 ms if 
the polarity is programmed as 1. You can program 
the time base and multiplier to increase the period 
during which the output operates.