ICP-CC488 | Installation Guide | 16.0  
Programmable Outputs 
EN | 76 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
Set DIP Switch 2 to the ON position for the Area 2 
codepad to operate correctly.  
Refer to Figure 16 on page 76 for the location of the 
DIP switches on the back of the codepad. 
 
Figure 16:  DIP Switch Location on Codepad 
 
 
1 – DIP switches 
16.3 Output 
Polarity 
There are fifteen different polarities. Each polarity is 
designated by a number that you program into the 
appropriate location for the output. 
Table 56:  Event Type Polarities 
 
Option 
Description 
0 Output 
not 
used 
Normally open, going low 
Normally open, pulsing low 
Normally open, one-shot low 
Normally open, one-shot low (reactivate)  
Normally open, one-shot low (can reset) 
Normally open, one-shot low (alarm) 
Normally open, latching low  
8 Normally 
low, 
going 
open 
Normally low, pulsing open 
10 
Normally low, one-shot open 
11 
Normally low, one-shot open (reactivate)  
12 
Normally low, one-shot open (can reset) 
13 
Normally low, one-shot open (alarm) 
14 
Normally low, latching open 
0 – Output Not Used 
If an output is not required, program the polarity as 
0. 
1 – Normally Open, Going Low 
This polarity is normally open circuit and switches to 
0 V when the event occurs. The output switches back 
to open circuit when the event is restored. Time 
parameters do not apply to this polarity. 
2 – Normally Open, Pulsing Low 
This polarity is normally open circuit and switches to 
pulsing 0 V when the event occurs. The output 
switches back to open circuit when the event is 
restored. Time parameters vary the On time of the 
pulse. 
3 – Normally Open, One-Shot Low 
This one-shot polarity is normally open circuit and 
switches to 0 V when the event occurs. The output 
switches back to open circuit when the time 
parameter setting expires. This one-shot time setting 
always runs its full duration and cannot be manually 
reset. 
4 – Normally Open, One-Shot Low with Reactivate 
This one-shot polarity is normally open circuit and 
switches to 0 V when the event occurs. Every time 
the event occurs, it restarts the one-shot timer. The 
output switches back to open circuit when the one-
shot time expires. This one-shot time setting always 
runs its full duration. You cannot reset the time. 
5 – Normally Open, One-Shot Low with Reset 
This one-shot polarity is normally open circuit and 
switches to 0 V when the event occurs. Because the 
output switches back to open circuit when the one-
shot time expires or when the event returns to 
normal, the operation of the output can be shortened 
regardless of the programmed time parameter. 
6 – Normally Open, One-Shot Low with Alarm 
This one-shot polarity is normally open circuit and 
switches to 0 V when the event occurs. The output 
switches back to open circuit when the one-shot time 
expires, the event returns to normal, or the system is 
disarmed.   
This polarity is ideally suited for the operation of 
strobe lights because you can program the lights to 
reset (up to 99 hours) and prevent them from burning 
out or bothering others due to prolonged operation. 
7 – Normally Open, Latching Low 
This polarity is normally open circuit and switches to 
0 V when the event occurs. The output switches back 
to open circuit when a user holds down [7] on the 
remote codepad until two beeps sound. Time 
parameters do not apply to this polarity. 
8 – Normally Low, Going Open 
This polarity is normally 0 V and switches to open 
circuit when the event occurs. The output switches 
back to 0 V when the event is restored. Time 
parameters do not apply to this polarity. 
9 – Normally Low, Pulsing Open 
This polarity is normally 0 V and switches to pulsing 
open circuit when the event occurs. The output 
switches back to 0 V when the event is restored. 
Time parameters vary the Off time of the pulse.