System Event Timers 
EN | 77 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
10 – Normally Low, One-Shot Open 
This one-shot polarity is normally 0 V and switches 
to open circuit when the event occurs. The output 
switches back to 0 V when the time parameter 
expires. This one-shot time setting always runs its full 
duration and cannot be manually reset. 
11 – Normally Low, One-Shot Open with 
Reactivate 
This one-shot polarity is normally 0 V and switches 
to open circuit when the event occurs. Every time the 
event occurs, it restarts the one-shot timer. The 
output switches back to 0 V when the one-shot time 
expires. 
12 – Normally Low, One-Shot Open with Reset 
This one-shot polarity is normally 0 V and switches 
to open circuit when the event occurs. Because the 
output switches back to 0 V when the one-shot time 
expires or when the event returns to normal, the one-
shot timer can be shortened regardless of the time 
setting. 
13 – Normally Low, One-Shot Open with Alarm 
This one-shot polarity is normally 0 V and switches 
to open circuit when the event occurs. Because the 
output switches back to 0 V when the one-shot time 
expires, the event returns to normal, or the system is 
disarmed, the one-shot timer can be shortened 
regardless of the time setting. 
14 – Normally Low, Latching Open 
This polarity is normally 0 V and switches to open 
circuit when the event occurs. The output switches 
back to 0 V when the user holds down [7] on the 
remote codepad until two beeps sound. Time 
parameters do not apply to this polarity. 
16.4 Output 
Timing 
The timing of outputs is calculated by the time base 
and a multiplier. These two values play different 
roles depending on the selected polarity. When you 
program outputs to pulse, you can set both the On 
and Off times. You can program one-shot polarities 
to operate from 200 ms to 99 hours. 
 
The maximum value you can program in 
the two multiplier locations is 9,9. 
 
Table 57:  Time Base Settings 
 
Option 
Description 
1 200 
ms 
2 1 
sec 
3 1 
min 
4 1 
hour 
You can only set the time base settings to one of the 
values listed in Table 57 on page 77. The multiplier 
value is a two-digit decimal number from 00 to 99. 
For greater accuracy, use 60 sec for 1-min intervals 
and 60 min for 1-hour intervals. 
16.5 Pulsing 
Polarities 
When programming pulsing polarities, you must set 
both the On and Off times. The duration, or On 
time, for an output is determined by time base 
selected from one of the options in Table 57 on page 
77. In other words, there are only four possible On 
times. 
The Off time is calculated by multiplying the On 
time by a decimal number between 00 and 99. If you 
want an output to operate for 200 ms every 5 sec, 
program the time settings as: 
On Time: 1 
Off Time: 2 5 
Table 58:  Pulsing Time Settings 
 
On Time 
Off Time 
Increments 
Tolerance 
200 ms 
200 ms to 
19.8 sec 
200 ms 
±200 ms 
1 sec 
1 to 99 sec 
1 sec 
±1 sec 
1 min 
1 to 99 min 
1 min 
±1 min 
1 hour 
1 to 99 hr 
1 hr 
± hr 
16.6 One-Shot 
Polarities 
The duration, or On time, of an output is determined 
by the product of the time base and the multiplier. 
If you want an output to operate for 5 sec, program 
the time settings as: 
Time Base: 2 
Multiplier: 0 5 
The On time is calculated by multiplying the time 
base setting (1 sec) by the multiplier value (05) (for 
example, 1 x 05  –  5 sec). 
Table 59:  One-Shot Time Settings 
 
On Time 
Increments 
Tolerance 
200 ms to 19.8 sec 
200 ms 
±200 ms 
1 to 99 sec 
1 sec 
±1 sec 
1 to 99 min 
1 min 
±1 min 
1 to 99 hr 
1 hr 
± hour 
17.0  System Event Timers 
This section covers the features that involve timing, 
such as Entry and Exit Times, Sensor Watch Time, 
Siren Run Time, and System Date and Time.