ICP-CC488 | Installation Guide | 18.0  
System and Consumer Options 
EN | 82 
 
 
Bosch Security Systems, Inc. | 12/08 | F01U089457-02 
 
2 – Ignore AC Fail 
If this option is selected, the MAINS indicator does 
not flash and the codepad does not beep every 
minute when the AC MAINS is disconnected from 
the control panel. If you want a programmable 
output to operate when the AC MAINS fails, use 
Output Event Type 1,4 AC Fail (refer to page 72). 
If this option is selected, an AC Loss report (Contact 
ID Event Code 301) still reports to the base station 
receiver unless Locations 416 and 417 are 
programmed as 0 (refer to Section 15.22 System Status 
– AC Fail Report 
on page 68). 
4 – Zone Pulse Count Handover 
If this option is selected, any zone pulse count 
readings are handed over and accumulate to any 
zone that is activated during the same arming cycle. 
Zone pulse count handover only operates with zone 
pulse count options 8 to 15. Refer to Section 14.3.3 
Zone Pulse Count
 on page 61 and Section 14.3.4 Zone 
Pulse Count Time
 on page 61 for more information. 
 
 
24-Hour Zones can receive any handover 
pulses from other zones. 24-Hour Zones 
cannot hand over pulses to other zones. 
8 – Handover Delay To Be Sequential 
If this option is selected, handover delay is sequential 
(that is, in numerical order from lowest to highest). If 
the sequence is broken before the Entry Time 
expires, an alarm occurs. If this option is not selected, 
handover delay follows the entry path if a Delay 
Zone is activated first. Refer to Section 14.3.2 Zone 
Types
 on page 61 for more information about 
Handover Zones. 
18.4 System 
Options 
Location 
495 
Default 
Panel to power up disarmed (if power reset) 
Arm/disarm tracking on power up 
Internal crystal to keep time 
Night arm station or RE005 installed 
1 – Panel To Power Up Disarmed 
If this option is selected, the control panel powers up 
in the disarmed state when the battery and AC 
MAINS are reconnected after the system is powered 
down. 
If this option is not selected, the system is always 
powered up armed in AWAY Mode. 
2 – Arm/Disarm Tracking on Power Up 
If selected, the control panel keeps its current armed 
status in non-volatile memory. If the control panel is 
restarted due to a power failure, the control panel 
returns to being armed or disarmed as it was before 
the power failed. 
Example 
If the system is disarmed when the system is powered 
down, the system returns to the disarmed state when 
the system is powered back up. 
4 – Internal Crystal To Keep Time 
If this option is selected, the control panel uses the 
internal crystal (XTAL) to keep track of time. This 
option is useful in countries that do not have a 
constant MAINS frequency. If this option is not 
selected, the control panel uses the MAINS 
frequency as a time base to keep time.  
8 – Night Arm Station, or RE005 Installed 
Select this option to use the RE005 2-Channel Radio 
Interface or the CP105 Night Arm Station. This 
option enables any of these three accessories to 
operate the control panel. User Code 16 is used to 
send Open/Close Reports when you use any of these 
accessories. 
 
The Night Arm Station cannot operate a 
partitioned ICP-CC488 Control Panel. 
18.5  Consumer Options 1 
Location
496 
Default 
Test reports only when armed 
Test report after siren reset 
Auto arm in STAY Mode 1 
STAY indicator to display Day Alarm status 
1 – Test Reports Only When Armed 
If this option is selected, Test Reports (Contact ID 
Event Code 602) are only sent when the system is 
armed. It is no longer necessary to send a Test 
Report with an Opening and Closing Report every 
day. 
Most commercial premises are open during the 
working week, so a Test Report is not necessary 
because Open and Close Reports are sent at the 
programmed time. If you want to manually send a 
Test Report, press and hold [9] button until two 
beeps sound. 
Refer to Section 15.28 Test Reporting Time to set the 
desired Test Report time. To set the first Test Report, 
refer to Section 5.1.2 Set the Number of Days until the 
First Test Report
2 – Test Report after Siren Reset 
Select this option to force the control panel to send a 
Test Report after the siren is reset. This can be used 
to indicate to the monitoring station that the control 
panel itself was not tampered with during the alarm 
period. 
4 – Auto Arm in STAY Mode 1 
Select this option if automatic arming in STAY Mode 
1 is preferred to automatic arming in AWAY Mode.