en | Description
Relay Unit
F.01U.278.516 | V1.0 | 2012.11
User Manual
Bosch Security Systems
2.2.4
RS-485 interface
One Main Unit and up to 32 Relay Units can be connected by a RS-485 bus. The bus must be 
connected to pins 2 and 5 of the RS-485 socket.
In this configuration, you always should connect the Main Unit first. The Relay Units must then 
be connected to the RS485-bus one by one, not at the same time.
Relay output
In the same connector, a potential free contact is available. It is a low current switching 
contact. The relay (potential free, switching power max. 48 V / 0.5 A) is activated at a call for 
help, call for assistance or fire alarm. This relay can be set as closing or switching contact 
(cycle of 10 seconds on / 10 seconds off). This feature can be used to drive a signal lamp for 
example.
For relay setting, see the user manual of the Main Unit.
2.2.5
Antenna
The antenna is connected to the Relay Unit using the adapter supplied with the unit.
NOTICE! 
Keep polarity equal when connecting further units to the RS485 bus!
NOTICE! 
Maximum RS485-bus length: 3’900 ft (1200 m).
Use only one twisted pair cable for the interconnection.
NOTICE! 
The receiver units located at the two ends of the bus must be terminated with a 100 Ohm 
jumper setting.