The gas supply lines must meet all requirements of the National Fuel Gas 
Code (ANSI Z223.1-Latest Edition), or in Canada CAN/CGA B149.1 Natural 
Gas Installation Code (Latest Edition) or CAN/CGA B149.2 Propane 
Installation Code (Latest Edition). 
 
The minimum permissible gas supply pressure for the purpose of input 
adjustment is one (1.0) inch (0.25 kPa) water column above the operating 
manifold pressure.  See the rating plate and gas valve for the manifold 
pressure and gas type.  The maximum permissible gas supply pressure is 
fourteen (14.0) inches (3.5 kPa) water column for natural gas and liquefied 
petroleum gases/propane gas. 
 
1.  Connect this water heater only to the type of gas (Natural or Propane gas) 
as shown on the rating plate.  Use clean black iron pipe or equivalent 
material approved by local codes and ordinances. (Dirt and scale from the 
pipe can enter the gas valve and cause it to malfunction).  The inlet gas 
line must have a minimum length of three (4) inches (7.6 cm) drip leg 
(sediment trap) installed as close to the water heater’s gas valve as 
possible.  A ground joint union must be installed in the gas supply line, as 
close to the water heater as possible, feeding the water heater to permit 
servicing of the water heater. Compounds used on the threaded joints of 
the gas piping must be resistant to the action of liquefied petroleum 
gases/propane gas.  DO NOT apply pipe dope to the gas valve inlet and 
make certain that no pipe dope has become lodged in the inlet screen of 
the gas valve.  Extreme care shall be taken to ensure no pipe dope enters 
the gas valve and to avoid excessive torque when tightening the gas 
supply line to the gas valve.  Excessive torque may result in cracking of 
the gas valve housing.  The suggested maximum torque is 31.5 ft. lbs. 
(4.4 kg-m).  The manufacturer of this water heater will not be liable for any 
damage or injury caused as a result of a cracked gas inlet as a result of 
excessive torque. 
2.  This water heater and its gas connection must be leak tested before 
placing the water heater in operation.  Check for gas leaks with a soap 
and water solution and a brush or a commercial leak detector fluid. 
NEVER USE A MATCH OR OPEN FLAME FOR TESTING! 
GENERAL OPERATION 
 
CAUTION 
The water heater and individual shutoff valve must be disconnected from 
the gas supply piping system during any pressure testing of the system at 
test pressures in excess of 1/2 psi (3.5 kPa).  The water heater must be 
isolated from the gas supply piping system by closing its manual shutoff 
valve during any pressure testing of the gas supply system at test 
pressures equal to or less than 1/2 psi (3.5 kPa).  The supply line must be 
capped when not connected to the water heater.
 