Regency U41-LP3 用户手册

下载
页码 24
9
Regency U41-3 ULTIMATE Gas Fireplace Insert
INSTALLATION
9 for spillage test.)
Before installing vent system ensure that the
damper plate is locked into the open position and
secure to prevent the damper plate from falling
down and crushing the liner.
GAS PRESSURE TEST
The unit is preset to give the correct gas input
at the specified manifold pressures shown on
the label. The maximum gas manifold pressure
is:
Natural Gas:
3.8" w.c.
Propane
11" w.c.
The manifold pressure is controlled by a regu-
lator built into the gas control, and should be
checked at the pressure test point. The pres-
sure check should be carried out with the unit
burning and the setting should be with in the
AERATION SYSTEM
The burner aeration is factory set but may need
adjusting due to either the local gas supply, air
supply or altitude.
Natural Gas:
3/16" open
Propane:
1/2" open
The aeration adjustment gears are located on
the right side of the burner box and can be
accessed from the side or from the front when
the louvers are removed.
limits specified.
Note: Use the same manner to check the
inlet pressure.
The Regency Insert incorporates its own inter-
nal draft hood, so no additional external draft
hood is required. Periodically check that the
vent is unrestricted
and an adequate
draft is present
when the unit is in
operation.  (See page
To adjust the aeration: use the allen key to turn
the turning gear which will adjust the air shutter.
Open the air shutter for a blue flame or close it
for a yellower flame.
Clockwise to open,
counter-clockwise to close.
Caution: Carbon will be produced if the
air shutter is closed too much.
Note: Any damage due to carboning re-
sulting from improperly setting
the aeration controls is NOT cov-
ered under warranty.
Note: Aeration Adjustment should only
be performed by an authorized
Regency Installer at the time of
installation or service.
TEST FOR FLUE
SPILLAGE
A “spillage” test must be made before the
installed unit is left with the customer.  Follow
the procedure below:
1) Start all exhaust fans in the home and then
close all doors and windows in the room.
2) Light the unit and set controls to maximum.
Turn fan off.
3) After five minutes, test that there is a “pull”
on the flue by placing a smoke match,
cigarette or similar device which gives off
smoke, in front of the spill tube. To ensure
a valid test, place a scrap piece of sheet
metal (or other non-combustible material)
between the spill tube and the upper lou-
ver, this will prevent the natural convection
of the unit from interfering with the test. See
diagrams below.
normal draft
downdraft or
blocked flue
Spill T ube
Non-combustible
Scrap 
The smoke should be drawn into the spill tube,
if it does not, leave the unit for a further five
minutes and retest as above. If the smoke is still
not drawn into the spill tube, turn the unit off and
check for the cause of the lack of draft. If
necessary, seek expert advice.
For wind turbulent sites, a wind cap may
remedy the problem.
Note: The thermally activated safety
switch will sense the change in