DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install and Connect Cabinets 
Page 1-18
Connect DC Power and Ground 
1
DC Power and Ground (J58890CF Only)
Figure 1-7
 shows a typical power and ground layout for a DC-powered cabinet. 
The size of the wire required for the -48 volt DC and -48 volt return must ensure 
the -48 volt DC supplied by the battery plant is maintained between -42.5 and 
-54.2 volts DC at all times for proper operation and to prevent hardware damage. 
This procedure applies to both PPN and EPN cabinets.
Figure 1-7.
Typical Power and Ground for a DC-Powered Cabinet