DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install and Connect Cabinets 
Page 1-19
Connect DC Power and Ground 
1
Connect DC Power and Ground
The grounding methods for the DC-powered system are more complex than that 
of an AC-powered system. The following installation procedures refer to 
. The numbers 1-8 in 
 match the following subsections 1-8. Other 
figures may be referenced as required.
!
CAUTION:
Grounding of the system shall comply with the general rules for grounding 
contained in Article 250 of the National Electrical Code, NFPA 70. For more 
information, refer to 
.
1. Install Coupled Bonding Conductor Wires
This is a conductor that connects to the single-point ground block and run 
adjacent to pairs in an associated cable. The mutual coupling between the CBC 
and the pairs reduces potential differences in terminating equipment. The 
conductor consists of a 10 AWG (#25) (6 mm
2
) wire terminated at the CBC 
ground terminal bar at the Main Distribution Frame (MDF).
1. At the DC Power Cabinet, connect a 10 AWG (#25) (6 mm
2
) ground wire to 
the Ground Discharge Bar. See 
2. Route the 10 AWG (#25) (6 mm
2
) ground wire to the CBC ground terminal 
bar at the MDF. Be sure a minimum of 12 inches (30.5 cm) spacing is 
maintained between the CBC and other power and ground leads.
3. Tie wrap the ground wire to the inside wiring cable.
NOTE:
The ground wires are connected to the CBC as instructed in 
‘‘Install Telecommunications Cabling’’
.
2. Connect DC Battery and Power Cabinet 
Grounds
1. Measure and cut a 6 AWG (#40) (16 mm
2
) wire (comcode 846110971) 
long enough to reach between the ground connection terminal in the DC 
Battery Cabinet and the Ground Discharge Bar in the DC Power Cabinet. 
See 
2. Crimp terminal lugs on each end of the wire. Terminal lugs are furnished 
as part of D-181895, Kit of Parts (comcode 105434559). 
3. At the DC Power Cabinet, connect the wire to the Ground Discharge Bar.
4. Route the wire through 1 of the holes in the side of the cabinets and 
terminate it on the Ground Connection Terminal in the DC Battery Cabinet.