Chapter 4 – Operation 
 
Setting Up the Inverter for Ethernet Network Operation 
 
Once the SJ-EN board has been properly configured and connected to a network as described in Chapter 3, it is 
capable of reading data from and writing data to the inverter. However if it is desired to have either the RUN 
command and/or the speed reference come from the Ethernet master, you must change two inverter parameters 
as shown in the following table. 
 
Defaults 
Function 
Code 
Name 
Description 
Run 
Mode 
Edit 
Lo Hi 
–FE 
(EU) 
–FU 
(US) 
–FR 
(Jpn) 
Setting for Ethernet Control 
A001 
Frequency 
Source 
Setting 
Six options; select codes: 
00 Keypad potentiometer 
01Control terminal 
02 Function F001 setting 
03 RS485 serial command 
04 Expansion board 1 
05 Expansion board 2 
8 8
01 01 01 
02 
A002 
Run 
command 
source setting 
Five options; select codes: 
01 Input terminal [FW] or [RV] 
(assignable) 
02 Run key on keypad, or 
digital operator 
03 RS485 serial command 
04 Start/Stop, expansion card #1 
05 Start/Stop, expansion card #2 
8 8
01 01 01 
02 
 
 
Supported MODBUS Functions 
 
The SJ-EN is implemented with the MODBUS/TCP communication protocol. It supports the following 
MODBUS functions: 
 
•  READ MULTIPLE REGISTERS (03) – This function reads the contents of a contiguous block 
of holding registers in the inverter. 
 
•  READ INPUT REGISTERS (04) – This function reads from 1 to up to around 125 contiguous 
input registers in the inverter. 
 
•  WRITE SINGLE REGISTER (06) – This function will write to a single holding register in the 
inverter. 
 
•  WRITE MULTIPLE REGISTERS (16) – This function will write to a block of contiguous 
registers in the inverter. 
 
Additional MODBUS/TCP protocol details, including specifications, application information, implementation 
guides, and other resources are available from the web site