Chapter 5 
 
 
Chapter 5 – Troubleshooting 
 
In general, the first step to troubleshooting should be to inspect the status LEDs on the SJ-EN board, in addition 
to the inverter operator/keypad display. These will give valuable clues to the nature of the problem. 
 
In addition, the inverter operator/keypad will provide diagnostic information for certain types of errors. Error 
codes for the option boards will have the format of: 
E6X.X
 for a board installed in option slot 1, or 
E7X.X
 for a board installed in option slot 2. The number 
to the right of the decimal point indicates the drive status at the time of trip, as follows: 
 
EXX.0 
At reset 
EXX.1 
At stop 
EXX.2 
During 
deceleration 
EXX.3 
At constant 
speed 
EXX.4 
During 
acceleration 
EXX.5 
f0 Stop 
EXX.6 
At starting 
EXX.7 
During DC 
injection 
braking 
EXX.8 
During overload 
restriction 
 
 
The digit immediately to the left of the decimal point has the following meaning: 
 
Code
 
Trip Name 
Cause 
Check 
Remedy 
Defective 
connection 
Connectors (plugs 
& jacks), cable 
Replace or repair; 
press STOP/RESET 
on inverter keypad 
PC not powered up 
or not connected to 
inverter 
That PC is powered 
on and connected 
Press STOP/RESET 
on inverter keypad 
EX0.X
 
Ethernet Communication 
Error 
Network 
configuration error 
Verify proper 
Ethernet setup of 
SJ-EN and master 
device  
Reconfigure 
incorrect settings. 
Option board ajar or 
loose 
Verify board is 
properly seated in 
connector 
Remove and reseat 
board 
Board lockup 
Check status LEDs 
Press STOP/RESET 
key on inverter or 
cycle power 
EX9.X 
Internal Communication 
Error (between SJ-EN and 
inverter) 
Board defective 
Check status LEDs 
Replace SJ-EN 
T T T T  
Inverter Mismatch 
(blinking display as shown) 
Inverter firmware 
version not 
compatible with 
SJ-EN option board 
Inverter 
Manufacturing 
Number for version 
(see Page 7) 
Replace Inverter 
with later version 