FPC-8057 User’s Manual 
common paired with a hot or signal line. 
If wiring is to be exposed to lightning or surges, use 
appropriate surge suppression devices. 
Keep AC, high energy, and rapidly switching DC 
wiring separate from signal wires. 
Equip ungrounded DC supplies with a resistor and 
capacitor in parallel to earth ground. This provides a path 
for static and high frequency dissipation. Typical values to 
use are 1MOhm and 4700pF. 
 
To make a connection, strip about 3/8” of insulation off the 
end of the wire, turn the connector screw 
counterclockwise until the gap is wide open, insert the 
wire all the way in, and turn the screw clockwise until it’s 
tight. 
Connection 
Connect positive DC line to the ‘+24V’ terminal and the 
DC ground to the ‘0V‘ terminal. 