GE 30 用户手册

下载
页码 88
 
GE
 
OPM_SGS_USM_10K_40K_0US_V010.doc 
37/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
Code 
Alarms 
Meaning 
4404 
K6 CLOSING 
FAILURE 
K6 open despite a closing command being issued. 
Signaled by auxiliary contact. 
The Load cannot be supplied by Automatic Bypass
4405 
K6 OPENING 
FAILURE 
K6 closed despite an opening command being issued. 
Signaled by auxiliary contact. 
4406 
SSM 
FAILURE 
A faulty current has been detected in the static-switch causing 
the opening of the contactor K6 for 10 sec. 
After 3 times K6 remains definitively open. 
The alarm reset can be done only from Service
4408 
K8 CLOSING 
FAILURE 
K8 not closed despite a closing command being issued. 
Signaled by auxiliary contact. 
The Load cannot be supplied by Automatic Bypass
4409 
K8 OPENING 
FAILURE 
K8 closed despite an opening command being issued. 
Signaled by auxiliary contact. 
4410 
BYPASS UTILITY 
OUT OF TOLERANCE 
The Utility Bypass Voltage is out of the tolerances (
±
 10%). 
K6 opens, synchronization with Utility is inhibited and transfer 
to Utility is blocked.
 
4420 
K3 CLOSING 
FAILURE 
K3 open despite a closing command. 
Inverter is switched OFF. 
It can be restarted manually after recovery of the alarm 
condition. 
4421 
K3 OPENING 
FAILURE 
K3 not open despite an opening command. 
Be aware the DC Capacitors could remain charged.
 
4520 
NO INVERTER 
POWER 
The Load supplied by Utility exceeds the Inverter power. 
The Load remains supplied by Utility until the alarm stays ON. 
4522 
FAN 
FAILURE 
A malfunction on the UPS ventilation system was detected. 
No change for UPS operation. 
Call immediately Service Center for intervention. 
4530 
LOAD LOCKED 
ON UTILITY 
Load is locked on Utility because 3 transfers on Utility have 
been detected in a short time (default 30 sec.). 
The transfer will be free after a time defined in parameter 
(default 30 sec.). 
4531 
LOAD ON UTILITY BY 
ERROR DETECTOR 
Load is transferred to Utility because the error detector 
detected a disturbance on the output voltage. 
4563 
EMERGENCY OFF 
ACTIVATED 
Alarm after detection of an EPO from an external safety 
device connected on Customer Interface Board. 
Consequently K3K4K6K7K8 open, RectifierInverter and 
SSM are switched Off. 
4570 
OVERLOAD 
The UPS-System is in an overload condition 
>
125% on 
Inverter, or 
>
150% on Utility
With Utility unavailable, a sequence of “stop operation” starts. 
Time out depends on Load quantity. 
4571 
OVERLOAD: 
LOAD ON UTILITY 
With  Utility Bypass supply available and load 
>
115%, the 
Load is transferred on Utility
Load will be transferred again automatically on Inverter when 
Load 
<
100%. 
4581 
INVERTER AND 
UTILITY NOT SYNCH. 
The voltages of Utility and Inverter are not synchronized, 
which causes the opening of K6