OPM_SGS_USM_10K_40K_0US_V010.doc 
38/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
Code 
Alarms 
Meaning 
4697 
BATTERY 
OVERTEMPERATURE 
Detection of Battery over temperature condition. 
Can be deactivated by Service
4698 
BATTERY POWER 
INSUFFICIENT 
In case of Utility Failure, with the actual Load, the run time 
would be below stop operation time (default 3 minutes). 
4700 
DC LOW 
Battery voltage is at the lowest limit. 
Will stay Off inverter until the battery voltage reaches the 
value in parameter. 
4900 
LOAD LOCKED 
ON INVERTER 
The Load is locked on Inverter after 3 Load transfers within 30 
seconds. 
After time out (default 30 sec.) Bypass will be free. 
4955  OVERTEMPERATURE 
An over-temperature condition has been detected on Inverter
Elapsed “stop operation” time, Inverter shutdown. 
With Utility OKLoad is transferred on Utility
4998 
LOAD OFF DUE TO 
EXTENT. OVERLOAD 
Load Off after time-out of “stop operation” for overload on 
Inverter or Bypass (time depending on the % of overload). 
4999 
LOAD OFF DUE 
TO UBATT. OR TEMP. 
Load Off after time-out of “stop operation” with missing Utility 
due to Battery low voltage or over-temperature condition.