OPM_SGS_USM_10K_40K_0US_V010.doc 
40/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
Code 
Message 
Meaning 
4535 
BYPASS 
LOCKED 
Bypass is not available. 
Contactor K6 and K8 are open, SSM deactivated.
 
4536 
BYPASS 
FREE 
Bypass is enabled. 
Contactor K6 is closed. 
4561 
TOTAL 
OFF 
Push-button  “total off” on the UPS Control Panel has been 
pressed, with the output circuit switch Q1 closed. 
4562 
DETOUR 
ON 
The auxiliary contact indicates that Manual Bypass Q2 was 
closed. 
4564 
DETOUR 
OFF 
The auxiliary contact indicates that Manual Bypass Q2 was 
opened. 
4567 
COMMAND 
LOAD ON UTILITY 
The control unit received a command to transfer the Load on 
Utility
4568 
COMMAND 
LOAD ON INVERTER 
The control unit received a command to transfer the Load on 
Inverter
4572 
NO MORE 
OVERLOAD 
End of the overload condition detected with alarm 4570. 
4580 
INVERTER AND 
UTILITY 
SYNCHRONIZED 
The voltages of Inverter and Utility Bypass are synchronized. 
4582 
COMMAND 
NOT TO 
SYNCHRONIZE 
Command not to synchronize with Utility
4583 
COMMAND TO 
SYNCHRONIZE 
Command to synchronize with Utility
4602 
Q1 
OPEN 
The auxiliary contact indicates that the output switch Q1 was 
opened. 
4603 
Q1 
CLOSED 
The auxiliary contact indicates that the output switch Q1 was 
closed. 
4699 
BATTERY TEST 
IMPOSSIBLE 
Automatic Battery Test is not possible due to: 
• 
No Utility Rectifier or Bypass. 
• 
Battery not fully charged. 
• 
Load is below 10% or above 80%. 
Test is postponed for 1 week. 
4763 
REMOTE CONTROL 
ON 
Inverter can be started or shutdown by remote control. 
Commands source can be chosen depending on the value of 
parameter (Service only): 
0   =  Only local panel. 
1   =  Only serial port on CI. 
2   =  Both.
 
4764 
REMOTE CONTROL 
OFF 
Inverter cannot be started or shutdown by remote control. 
Commands source can be chosen depending on the value of 
parameter (Service only): 
0   =  Only local panel. 
1   =  Only serial port on CI. 
2   =  Both.