26
The 
fan 
doesn
’t run 
1.  Check if any connection has come off. 
2.  Check is the fan is burned. 
1. Change the fan. 
 
2. Change the fan. 
Electricity 
leakage 
of 
temperature 
controller 
1.  The service time is too long. 
 
2.  The environment is too dirty. 
3.  Humidity is too high. 
1.  Change temperature controller. 
2.  Use brush to remove dust. 
3.  Make  the  temperature  dry  and 
control the environment humidity. 
Temperature 
controller  out 
of order 
1.  There  is  leakage  of  temperature 
sensing medium. 
2.  Damage  of  cam  of  contacting  point 
spring, etc. 
Change temperature controller. 
The  probe  of 
temperature 
sensing  tube 
doesn
’t 
contact 
evaporator 
well 
It  has  not  been  mounted  to  position  or 
changed during transportation. 
Mount it again. 
12.1.12 Procedure for fan change 
(1) Switch off power and open the fan protection cover. 
(2) Remove the fan bolts by using fork wrench or universal tool. 
(3) Loose the fan blade and take it out. 
(4) Take the fan out from the space between compressor and tubes. 
(5) Mount new fan from the space between the compressor and tubes, put 
blade onto position and secure it by using a fork wrench or universal 
tool. 
(6) Make a test run; check if the operation is normal, if there is any blocking 
of blade. 
(7) 
Make  sure  not  to  bend  or  damage  tubing  during  removal  and 
installation.
 
MAINTENANCE SERVICE AND TROUBLE SHOOTING
 
Maintenance Service and Trouble Shooting
 
12.1.13 Procedure for temperature controller change 