Configuring via the Web Server
Configuring the System
Steps
: Use the descriptions in the following table to configure each group:
Table 2-12:  Configuration > Other I/O & Groups > Groups Tab Field Descriptions
Setting
Description
Name
Enter a unique name to identify the group.
Pulse Time
Specifies the duration for which the device will assume 
abnormal status. For example, it specifies how long a horn will 
blow or a door strike will remain released. The maximum 
number of hours is 1. When the hour field is blank, the 
maximum number of minutes is 59. When 1 is entered in the 
hour field, the maximum number of minutes is 45. The sum of 
all three units comprises the pulse time. Note that you can 
express seconds in tenths of a second.
Energized TZ
Specifies the period during which the group of output relays are 
automatically energized.
Interlock Disabled 
TZ
Specifies the period during which the interlocks that control the 
group’s outputs will be disabled.
Latch
Toggles the state of the outputs between energized and 
de-energized status upon every activation (code use, interlock, 
or manual pulse).