Quantum acl 4 安装指导

下载
页码 68
Chapter 1 Installation Requirements
Library Specifications
ACL 4/52 Facilities Planning and Installation Guide
Library Specifications
1
The tables in this section provide the mechanical, power, and 
environmental specifications for the Enterprise library. Use these 
specifications to help select an appropriate installation site and 
environment.
Figure 1  Library Mechanical 
Specifications
Figure 2  Library Power 
Specifications
Figure 3  Library Environmental 
Specifications
Height
44 inches (111.76 cm)
Width
21.5 inches (54.61 cm)
Depth
31.12 inches (79.04 cm)
Weight
361 lbs. (164 kg) with 4 tape drives and 52 DLT cartridges
AC Power Rating
100–120V/200-240V, 4A/2A, 50/60 Hz
AC Voltage Range
90–132 VAC or 180–264 VAC
Frequency Range
47–63 Hz
Temperature:
Storage—Short-Term (<60 Days)
Storage—Long-Term (>60 Days)
Transport
Operating
-40 to 151
°
F (-40 to 66
°
C)
41 to 122
°
F (5 to 50
°
C)
-40 to 151
°
F (-40 to 66
°
C)
59 to 90
°
F (15 to 32
°
C)
Relative 
Humidity:
Non-Operating (Storage)
Non-Operating (Transport)
Operating
95% (Wet bulb temp = 90
°
F/32
°
C)
95% (Wet bulb temp = 115
°
F/46
°
C)
20–80% (Wet bulb temp = 
77
°
F/25
°
C)
Altitude:
Short-Term (<60 days in storage)
Long-Term (>60 days in storage)
Operating
12,000 ft (3,658 km)
12,000 ft (3,658 km)
6,562 ft (2.0 km) @ 76
°
F Max. 
& 589 mmHg
Heat 
Dissipation:
Operating
880 BTU/hr (220 KCal/hr or 260 
watts)