Specifications – General, 
Continued
 
Physical 
 
Model # 
Torque 
 lb-ft (N_M) 
Output 
Shaft Size 
Shaft Key 
Size 
Output 
Shaft 
Length 
Maximum 
Overhang 
Load 
Handwheel 
Diameter 
Approx. 
Maximum 
Weight 
11284S 425 
(576) 
2" 
(51 mm) 
1/2" 
(13 mm) 
5" 
(127 mm) 
3700 lb. 
(1678 kg) 
18" 
(457 mm) 
300 lb. 
(136 kg) 
11285S 840 
(1139) 
2" 
(51 mm) 
1/2" 
(13 mm) 
5" 
(127 mm) 
3700 lb. 
(1678 kg) 
18" 
(457 mm) 
300 lb. 
(136 kg) 
11286S 1500 
(2033) 
2" 
(51 mm) 
1/2" 
(13 mm) 
5" 
(127 mm) 
3700 lb. 
(1678 kg) 
18" 
(457 mm) 
300 lb. 
(136 kg) 
11288S 2500 
(3389) 
2-1/2" 
(64 mm) 
5/8" 
(16 mm) 
6" 
(152 mm) 
7500 lb. 
(3402 kg) 
18" 
(457 mm) 
550 lb. 
(251 kg) 
11289S 4000 
(5423) 
2-1/2" 
(64 mm) 
5/8" 
(16 mm) 
6" 
(152 mm) 
7500 lb. 
(3402 kg) 
18" 
(457 mm) 
600 lb. 
(272 kg) 
11287S 5500 
(7457) 
2-1/2" 
(64 mm) 
5/8" 
(16 mm) 
6" 
(152 mm) 
7500 lb. 
(3402 kg) 
18" 
(457 mm) 
600 lb. 
(272 kg) 
 
Electrical 
Mains Supply 
115/220 Vac, single phase 50/60 Hz up to 1500 lb-ft 
208/200 – 240/380 – 480/575 Vac, three phase 50/60 Hz 
Motor 
Inverter rated, continuous duty, C face mounting 
Motor Current 
Motor Size 
Full Load Amps (FLA) 
 
(Horsepower) 
@ 230 Vac 
@ 460 Vac 
 
½  
¾ 
1 ½ 

1.6 
2.2 
2.6 
4.4 
5.6 
7.8 
0.8 
1.1 
1.3 
2.2 
2.8 
3.9 
Loss of Power 
Stays in place 
Local Auto - Manual 
Switch 
Allows local manual and automatic operation of the actuator 
Limit Switches 
Standard - Two SPDT end-of-travel limits rated 10 A at 125 Vac, 5 A at 250 Vac. 
Auxiliary 
Switches/Relays 
Optional – Up to 2 additional SPDT switches (or 4 relay outputs, programmable) 
Installation Category 
(Overvoltage Category) 
Category II:  Energy-consuming equipment supplied from the fixed installation.  Local level 
appliances, and industrial control equipment.  (EN 61010-1) 
Pollution Degree 
Pollution degree 2:  Normally non-conductive pollution with occasional conductivity caused by 