Honeywell 11280s 用户手册

下载
页码 14
61-86-03-13 
Page 7 
 
Specifications – Actuator  
Electrical 
Input Signals 
Analog:  0/4 to 20 mA  (With supplied 250 ohm shunt resistor for current range) 
 
0/1 to 5 Vdc  
 
0 to 10 Vdc 
Digital:   Remote Setpoint via Modbus RTU (RS485) 
Input Impedance 
 
Input 
 
0/4 to 20 mA 
 
0/1 to 5 Vdc 
Input Impedance 
 250 
ohms 
 
10 K ohms  
Input Characterization 
Provides characterization of the input signal.  
Selections are:  Linear, Square Root or Custom.  
Sensitivity 
0.2 % to 5 % of 90° span, proportional to deadband 
Hysteresis 
Less than 0.4 % of full scale 
Deadband 
0.2 % to 5 % of 90° span, adjustable.  Shipped at 0.5% 
Repeatability 
0.2 % of 90° span 
Voltage/ Supply Stability 
0.25 % of span with +10/
-
15 % voltage change 
Temperature Coefficient 
Less than 
± 0.030 % of span per degree C for 0 °C to 50 °C 
Less than 
± 0.05 % of span per degree C for 
-
30 °C to 65 °C 
Zero Suppression 
90% of span 
Input Filters 
Selectable spike and low pass filters 
Solid State Motor Control 
CW/CCW open collectors (opto-isolators) for use as discrete control inputs to the inverter 
for motor operation.  
Failsafe operation 
If input signal exceeds configured input range.  Selectable and adjustable. 
Feedback signals/Output 
0 to 20 mA, 4 to 20 mA 
0 to 5 Vdc, 1 to 5 Vdc with 250 ohm resistor; (0 to 16 Vdc with 800 ohm resistor) 
Slidewire Emulation 
Provides output voltage ratiometric to shaft position and potentiometric to supply voltage 
(1 to 20 Vdc) without a slidewire. Emulates a 100 ohm to 1000 ohm slidewire. 10 mA 
output maximum. 
Isolation 
Input signal, output signal and power are isolated from each other.  
Load Requirement (4-20) 
Current Out — 0 to 1000 ohms 
Programmable Functions 
Selectable and configurable operating parameters: 
 
• 
Input range 
• 
Input filtering 
• 
Input characterization 
• 
Security 
• 
Digital Input action 
• 
Deadband 
• 
Failsafe on loss of 
input signal 
• 
Failsafe on loss of 
position sensor 
• 
Direction of rotation 
• 
Relay closure 
action 
• 
Communication 
parameters 
• 
Split range 
operation 
• 
Output range 
• 
Alarms