Toshiba 18 - 1250 A 用户手册

下载
页码 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
79 
F033 =  Event #1 Start Time 
Factory Setting = OFF  
Range = 00:00 through 23:59, or OFF 
This function is used to select the start time for Event #1 in the 
TCC above. Once given a Start command after this event time, 
the starter will run the motor according to the selections entered 
into F030 and for the time entered into F031. 
F034 =  Event #2 Start Time Same as above, except for event #2 
F035 =  Event #3 Start Time Same as above, except for event #3 
F036 =  Event #4 Start Time Same as above, except for event #4 
F037 =  Event #5 Start Time Same as above, except for event #5 
F038 =  Event #6 Start Time Same as above, except for event #6 
F039 =  Event #7 Start Time Same as above, except for event #7 
ƒ  NOTE: 
Start Events are completely independent of one another, and can 
be programmed in any order. For instance, the Start Time in F037 
can be earlier than the Start Time in F033. This allows easier 
alterations or additions of new Start Times after a unit is already 
installed.