Toshiba 18 - 1250 A 用户手册

下载
页码 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
81 
Display
Pre ss
Ke y...
Shows...
M eans...
Starting at
Function #30
Default Se tting
of Function #30
Se t F030 = 1
M in.  Batch  Timer
Se t to 17.30
(5:30 PM  military)
Se t to 2:
Ev e ry 2nd  Day
F030
0000
0001
17..30
0002
 End
Value Acce pte d
(flashe s once)
Re turn to
Function # Display
Figure App 4.3: Program m ing Tim er Functions
Example: Process Timer and TCC
for Irrigation Pump
F033
READ
ENTER
READ
ENTER
x 3
x 2
Change Se tting
to 30 minute s
0030
READ
ENTER
 End
Value Acce pte d
(flashe s once)
Change  to
F031
F031
Default Se tting
of Function #31
0000
READ
ENTER
READ
ENTER
 End
Value Acce pte d
(flashe s once)
Change to
F032
F032
Default Se tting
of Function #32
0000
READ
ENTER
READ
ENTER
 End
Value Acce pte d
(flashe s once)
F033
Change  to
F033
Cycle Control Powe r to Acce pt Change s
 
 
Example: Figure App 4.3 
 Time Clock Controller with Minimum Run Timer  
 
 
An irrigation pump fed from a well with a single float level control 
needs to come on every other day at 5:30 PM, and run for ½ hour. 
If during that ½ hour the well level drops and shuts the pump 
down, the pump needs to restart when the well recovers and finish 
the ½ hour pump time. 
 
Set F030 to [0001] for Minimum Run Timer
This will ensure that when the well level recovers and resets the 
run command, the starter will finish the time sequence. 
Set F031 to [0030] (minutes) 
This is the Batch Time that ensures the proper amount of irrigation 
getting to the crop. 
Set F032 to [0002] for Every 2
nd
 Day 
This will begin the Start Even Cycle on the day of programming 
and every other day from then on.  
Set F033 to [17.30] 
This is the 24HR time value representing 5:30 PM. At this time, 
every other day, the TE Series starter will automatically start 
(provided the Stop float in the well is closed) and run for 30 
minutes as programmed in F030. 
 
 
If the pump needs to come on again at 7:00 PM, program F034 to 
[19.00]. If later on it is needed to come on at 6:00 AM as well, 
simply change any other unused start time, i.e. F038 to [06.00]. 
Even though this is Event #6 and the lower numbered events had 
later start times in the program, the starter will execute #6 on time 
in the next available cycle. 
 
If the pump needs to come on every day, program F032 to [0001].
 
 
 
 
 
 
 
 
 
ƒ  NOTE:  
If programming is entered AFTER the set time value, the TCC will 
wait until the next valid time before executing (i.e. if you entered the 
above example program changes at 5:35 PM, the pump would not 
come on automatically until 5:30 PM 2 days from now).