Toshiba 300 KW 用户手册

下载
页码 80
61
G8000 Series Installation and Operation Manual
14.7    Changing Between Float Charge and Equalize Charge
The procedure to change the recharge mode between float charge and equalize charge is shown in 
Steps 1-3.
See the Note below for an explanation of Float and Equalize charge modes.
STEP 1
Make sure that the FLOAT CHARGE LED 
is “ON”. 
STEP 2
Press FLOAT/EQUAL button for at least 
0.5 sec.
Change completed.
EQUAL CHARGE LED is “ON”.
FLOAT CHARGE LED is “OFF”
STEP 3
Please wait until procedure is completed.
NOTE
In equalize charge mode, the battery 
is charged for a programmed period at 
a specified voltage (depending on the 
battery spec), rather than the float charge, 
in order to prevent voltage deviations 
among battery cells. This should be done 
once every six months if possible.
The G8000 UPS will automatically perform 
the equalize recharge after battery backup 
operation.
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
UPS SUPPLY
AC - Vo  480 V
AC - Io  50%  
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
UPS SUPPLY
AC - Vo  480 V
AC - Io  50%  
LED Key 
        - LED Off 
        - LED On 
        - LED Flash