14.8    Changing to Float Charge from Protection Charge (If applicable)
The  manual  procedure  to  change  from  protection  charge  to  float  charge  is  shown  in  Step  1-3.This 
operation applies to batteries after they have experienced over temperature condition.
See the Note below for an explanation of float charge and protection charge.
STEP 1
Make sure that the EQUAL CHARGE LED 
is “ON”. 
STEP 2
Make sure that the “BATT FAULT1” warning 
goes away.
STEP 3
Press “FLOAT/EQUAL” button for at least 
0.5 seconds.
Procedure completed.
NOTE
The battery is normally being charged at float 
charge mode. To prevent thermal runaway 
of the battery, this mode will automatically 
be changed to protection charge when a 
“BATT FAULT1” (Battery over temperature) 
warning occurs.
In protection charge mode, the battery is 
automatically charged at a voltage about 5% 
lower than float charge.
If the “BATT FAULT1” warning message goes 
away and a programmed duration is elapsed 
(about 24 hours), this mode will automatically 
be changed back to float charge. Thus, it is 
not usually required to change the recharge 
mode manually back to the float charge.
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
UPS SUPPLY
AC - Vo  480 V
AC - Io  50%  
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
UPS SUPPLY
AC - Vo  480 V
AC - Io  50%  
LED Key 
        - LED Off 
        - LED On 
        - LED Flash