Honeywell PUB1012S Benutzerhandbuch

Seite von 24
SPYDER® BACNET® PROGRAMMABLE CONTROLLERS
7
63-2689—05
The application engineer must review the control job 
requirements. This includes the sequences of operation for the 
controller, and for the system as a whole. Usually, there are 
variables that must be passed between the controller and other 
Spyder BACnet controller(s) that are required for optimum 
system wide operation. Typical examples are the TOD, Occ/
Unocc signal, the outdoor air temperature, the demand limit 
control signal, and the smoke control mode signal. 
It is important to understand these interrelationships early in 
the job engineering process, to ensure proper implementation 
when configuring the controllers. Refer to the controller 
Application Guides. 
Power Budget
A power budget must be calculated for each device to 
determine the required transformer size for proper operation. A 
power budget is simply the summing of the maximum power 
draw ratings (in VA) of all the devices to be controlled. This 
includes the controller itself and any devices powered from the 
controller, such as equipment actuators (ML6161 or other 
motors) and various contactors and transducers. 
IMPORTANT
• When multiple controllers operate from a single 
transformer, connect the same side of the transformer 
secondary to the same power input terminal in each 
device. The earth ground terminal (terminal 3) must 
be connected to a verified earth ground for each 
controller in the group (see Fig. 12 on page 9).
• Half-wave devices and full-wave devices must not use 
the same AC transformer. If a Spyder controller will 
share its power supply with another device, make 
sure the other device utilizes a half-wave rectifier and 
that the polarity of the wiring is maintained.
POWER BUDGET CALCULATION EXAMPLE
Table 3 is an example of a power budget calculation for a 
typical PVB6436AS controller. While the example is shown for 
only this model, the process is applicable for all controller 
models.
Table 3. Power budget calculation example.
The system example above requires 30.7 VA of peak power. 
Therefore, a 100 VA AT92A transformer could be used to 
power one controller of this type. Because the total peak power 
is less than 33 VA, this same transformer could be used to 
power three of these controllers and meet NEC Class 2 
restrictions (no greater than 100 VA). 
See Fig. 11–Fig. 12 beginning on page 9 for illustrations of 
controller power wiring. See Table 4 for VA ratings of various 
devices.
Table 4. VA ratings for transformer sizing.
For contactors and similar devices, the in-rush power ratings 
should be used as the worst case values when performing 
power budget calculations. Also, the application engineer must 
consider the possible combinations of simultaneously 
energized outputs and calculate the VA ratings accordingly. 
The worst case, which uses the largest possible VA load, 
should be determined when sizing the transformer. 
Each controller requires 24 Vac power from an energy-limited 
Class II power source. To conform to Class II restrictions (U.S. 
only), transformers must not be larger than 100 VA. A single 
transformer can power more than one controller.
GUIDELINES FOR POWER WIRING ARE AS FOLLOWS:
— For multiple controllers operating from a single 
transformer, the same side of the transformer 
secondary must be connected to the same power input 
terminal in each device. The earth ground terminal 
must be connected to a verified earth ground for each 
controller in the group (see Fig. 12 on page 9). 
Controller configurations are not necessarily limited to 
three devices, but the total power draw, including 
accessories, cannot exceed 100 VA when powered by 
the same transformer (U.S. only).
— See Fig. 11 on page 9 for controller power wiring used 
in UL 1995 equipment (U.S. only).
— Many controllers require all loads to be powered by the 
same transformer that powers the controller.
— Keep the earth ground connection wire run as short as 
possible (refer to Fig. 11–Fig. 12 beginning on page 9).
— Do not connect earth ground to the controller’s digital or 
analog ground terminals (refer to Fig. 11 and Fig. 12).
— Unswitched 24 Vac power wiring can be run in the 
same conduit as the L
ON
W
ORKS
® Bus cable.
Line-Loss
Controllers must receive a minimum supply voltage of 20 Vac. 
If long power or output wire runs are required, a voltage drop 
due to Ohms Law (I x R) line-loss must be considered. This 
line-loss can result in a significant increase in total power 
Device
VA
Information
Obtained From
PVB6436AS 
controllers (include 
Series 60 Floating 
Damper Actuator)
9.0
R8242A Contactor 
fan rating
21.0
TRADELINE
®
 Catalog 
inrush rating
D/X Stages
0.0
For example, assume 
cooling stage outputs are 
wired into a compressor 
control circuit and have no 
impact on the budget.
M6410A Steam 
Heating Coil Valve
0.7
TRADELINE
®
 Catalog, 
0.32A 24 Vac
TOTAL
30.7
Device
Description
VA
PVB6436AS 
controllers and 
Series 60 Floating 
Damper Actuator
Controller and Actuator
9.0
PUB6438S or   
PVB6438NS
Controller
5.0
ML684
Versadrive Valve Actuator
12.0
ML6161
Damper Actuator, 35 lb-in.
2.2
ML6185
Damper Actuator SR 50 lb-in
12.0
ML6464
Damper Actuator, 66 lb-in.
3.0
ML6474
Damper Actuator, 132 lb-in.
3.0
R6410A
Valve Actuator
0.7
R8242A
Contactor
21.0