NFPA Standard-Specific Requirements
Central Station/Remote Station Transmitter: Connection to FACP Dry 
122
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
C.2  Central Station/Remote Station Transmitter:
        Connection to FACP Dry Contacts
The dry contacts of the MRP-2001/E  programmable relays can be used to trip a UL-864 Listed 
Central Station/Remote Station Transmitter.  The FACP contacts must be supervised by the Central 
Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value 
determined by the Transmitter manufacturer.  Power is also provided by the Central Station/Remote 
Station Transmitter manufacturer.  Refer to the Central Station/Remote Station Transmitter 
manufacturer’s manual for details. 
Figure C.5 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter
Typical Central Station/Remote Station Transmitter Module
Typical Input Zone Triggers
Fire Alarm Control Panel
Al
ar
m
Superv
.
T
ro
ubl
e*
*Note:  The Trouble Relay is a 
fail-safe relay.  With power 
applied to the FACP and no 
troubles in the panel, the wiring 
should be connected to the NO 
and C contacts as indicated in the 
illustration.
rp2002drysmi
t.cdr